Specifications

Installation Reference
Eaton PDU (150 kVA) Installation and Operation Manual 164202126—Rev 5 www.eaton.com/powerquality A-3
The PDU cooling requirements are shown in Table D.
Table D. PDU Cooling Requirements During Full Load Operation
Rating Voltage Heat Rejection
kVA K-factor Input Output Watts BTU/hr Kg-cal/hr
50 13 208 208/120 1118 3814.77 961.31
50 13 480 208/120 2018 6885.70 1735.17
50 20 480 208/120 2020 6892.53 1736.89
75 13 208 208/120 2640 9008.05 2269.99
75 13 480 208/120 3415 11652.46 2936.37
75 20 480 208/120 2214 7554.48 1903.70
100 13 480 208/120 5590 19073.87 4806.53
100 20 480 208/120 5438 18555.22 4675.84
125 13 480 208/120 3872 13211.81 3329.32
125 20 480 208/120 2903 9905.45 2496.13
150 20 208 208/120 3200 10918.85 2751.50
150 13 480 208/120 5506 18787.25 4734.31
150 20 480 208/120 5410 18459.68 4651.76
150 13 600 208/120 3445 11754.83 2962.17