Specifications
Scope of Work Attachment L-2
Revised 12/12
Page 2 of 3
6. BATTERY SET-UP
6.1. Determine common or separate battery set-up process and settings
6.2. Check for proper cell interconnections with respect to polarity throughout battery.
6.3. Check battery configuration matches required unit configuration (voltage, polarity, number of cells
per string)
7. BRANCH CIRCUIT MONITORING SET-UP (if optionally purchased)
7.1. Ensure installation configuration matches application
7.2. Perform branch circuit breaker scheduling
7.3. Check voltage and current calibrations
8. OPERATIONAL INSPECTION
8.1. Check proper system operation in Normal Mode, Bypass Mode, and Battery Mode
8.2. Check system transitions between operating modes
8.3. Check multi-module operations
8.4. Verify system calibrations and adjust as necessary
9. FUNCTIONAL TEST
9.1. Test Battery mode
9.2. Simulate the loss of bypass when on battery testing
9.3. Perform ISBM loss of logic power testing
9.4. Emergency transfer testing
9.5. Local and Remote Emergency Power Off testing
9.6. Mini CSB Failure testing
9.7. Fan Failure Test (ONLY PERFORM IF NO LOAD IS APPLIED)
9.8. Building Alarms testing
9.9. Basic Easy Capacity testing
10. INSTALL OPTIONAL CONNECTIVITY AND MONITORING
10.1. Upon customer enrollment and request (www.powerquality.eaton.com/enotify, select
“Install eNotify”, and complete an “eNotify Request Form”), install and program connectivity parts
and test monitoring connection. Customer must enroll and authorize Eaton to provide monitoring
(connectivity parts may require separate purchase); customer may self install eNotify or
purchase a separate installation if not completed at startup.
11. INSPECTION COMPLETION
11.1. Ensure dead fronts and door panels are reinstalled
11.2. System will be left in normal mode when environmental controls are operational
11.3. Conduct on-site customer system operation training
11.4. Final EEPs, calibration EEPs, meters report, service log, and configuration reports will be
downloaded and stored
11.5. Startup data forms and reports are available as required.
11.6. Clean up tools and debris around the system.
FLYWHEEL UNITS ONLY (Varies by Flywheel type)
1. MECHANICAL INSPECTION