Datasheet

23
TECHNICAL SPECIFICATION 7 kVA 11 kVA
Technology online double conversion with PFC (Power Factor Correction) system
(1)
Active power kVA / kW 7 / 4.9 11 / 8
Rated input voltage 200/208/220/230/240/250V single phase or 380/400/415V three phase
Input voltage range (- 30%; + 20%) 230 V; (- 20%, + 15%) 400 V (- 30%; + 20%) 230 V; (- 20%, + 15%) 400 V
Input, output frequency range 40-70 Hz, 50 / 60 HZ autoselection, frequency converter as a standard
Output voltage / THDU 200/208/230/240 /250 V +/- 2%; THDU < 2% 200/208/230/240 /250 V +/- 2%; THDU < 2%
Overall efficiency normal mode 91%, eco mode 97% normal mode 91%, eco mode 97%
THDI THDI < 5%
(2)
THDI < 5%
(2
Crest factor / short circuit current 3:1 / 100 A 3:1 / 150 A
Overload capacity >150% 500 ms; 150% 30 s; 125% 60 s; 110% 120 s >150% 500 ms; 150% 30 s; 125% 60 s; 110% 120 s
Temperature operating 45°C for 8 Hrs
(3)
, 40°C continuous 45°C for 8 Hrs
(3)
, 40°C continuous
Back-up times
(4)
at 70% load
from 10 up to 15 min Standard: 1 power mod. 3U + 1 battery mod. EXB 3U
= 6U
Standard: 1 power mod. 3U + 1 battery mod. EXB 3U
= 6U
from 15 up to 20 min Standard + 1 battery mod. EXB 3U = 9U Standard + 1 battery mod. EXB 3U = 9U
from 40 up to 65 min Standard + 2 battery mod. EXB 3U = 12U Standard + 2 battery mod. EXB 3U = 12U
Connection
Input /output terminal block for 13 mm
2
(stranded cable) or 10 mm
2
(solid cable)
Communication
Port type 6 voltage free contacts DB9 2 A 48 V DC, 1 RS 232, RJ11 for remote emergency power off
Slot 1 slot for inter-unit communication card 1 slot for inter-unit communication card
Standard and certification
Performance and safety IEC 62040-1/IEC 60950/UL 1778 and CSA 22.2
(1)
IEC 62040-1/IEC 60950/UL 1778 and CSA 22.2
(1)
EMC IEC 62040-2; EN 50091-2; FCC class A
(1)
, EMC B level
(5)
IEC 62040-2; EN 50091-2; FCC class A
(1)
, EMC B level
(5)
Certification UL(2)/TÜV, GS mark,CB, C-Tick,CE, IEC 68-2-6 (vibration tests Marine approval)
Dimension (HxWxD in mm) ; weight (single phase input / three phase input)
EX RT standard backup tower 444.5x261.2x700
88.3 kg / 89.5 kg
444.5x261.2x700
94.2 kg / 95.3 kg
EX RT standard backup Network Pack
rack mounting
261.2 (6U) x444.5x700
96.1 kg / 97.3 kg
261.2 (6U) x444.5x700
102 kg / 103.1 kg
Comet EX RT Power module 444.5x130.6x700 / 130.6 (3U) x444.5x700
23 kg / 24.2 kg
444.5x130.6x700 / 130.6 (3U) x444.5x700
24.9 kg / 26 kg
Battery module EXB RT 444.5x130.6x650 / 130.6 (3U) x444.5x650
64.5 kg
444.5x130.6x650 / 130.6 (3U) x444.5x650
68.5 kg
EX RT CLA module / EX RT Transformer 130.6 (3U) x444.5x650 / 12 kg / 87 kg 130.6 (3U) x444.5x650 / 12 kg / 87 kg
Part number
Single phase 68070 68110
Three phase 68074 68114
EXB 68078 68118
1: applicable to single phase models.
2: single phase input value.
3: at nominal output power for 230 V or 400V input and 230V output.
4: typical values after 3 discharge cycles, batteries 3-5 years, longer backup times available using the CLA or EXB module, ask for details. 5: option for single phase model.