Datasheet

21
TECHNICAL SPECIFICATION 5 kVA 15 kVA 20 kVA
Rating (kVA) / (kW) 5 kVA / 4,5 kW 15 kVA / 13, 5 kW 20 kVA
/ 18 kW
Technology VFI-SS-113, online double conversion with power factor correction, convection cooled static bypass switch
Paralleling
Maximum rating / redundancy
(1)
10 kVA / 5 kVA + 5 kVA redundancy 15 kVA / 10 kVA + 5 kVA
redundancy / 5 kVA + 2 x 5 kVA
redundancy
20 kVA / 15 kVA + 5 kVA
redundancy / 10 kVA + 2 x 5 kVA
redundancy
Input
Number of phase, input connection L + N, terminals up to 6 mm
2
L + N or 3P + N, terminals up to 35 mm
2
, separate or common AC normal
and AC bypass
Nominal voltage 200/208/220/230/240/250 V 200/208/220/230/240/250 V (L + N) or 380/400/415 V (3P + N)
Voltage range without using battery
(2)
120 - 280 V 120 - 280 V (L + N), 250 - 465 V (3P + N)
Input frequency range, THDI 40-70 Hz, < 7% 40-70 Hz, < 7% 40-70 Hz, < 7%
Output
Output connection
(3)
terminals + 8 IEC C13 (10A) + 2 IEC
C19 (16A)
terminals + 8 IEC C13 (10A) + 4 IEC C19 (16A)
Remotely controlled Powershare socket 2 groups (2 IEC C13 10A per group) 2 groups (2 IEC C13 10A per group) 2 groups (2 IEC C13 10A per group)
Output voltage and frequency
(4)
, THDU,
efficiency
(5)
200/208/230/240 /250 V, 50 / 60 Hz autoselect, frequency converter as standard, <2%, 97%
Backup time
MX standard backup time @ 70% load 10 min 8 min 8 min
MX + EXB / MX + 2 EXB / MX + 3 EXB 35 / 60 / 95 min 35 min (3 EXB)/60 min (6 EXB)/90
min (9 EXB)
(7)
35 min (4 EXB)/60 min (8 EXB)/90
min (12 EXB)
Communication
Slot 1 slot or 2 slots (Frame) compatible with ConnectUPS, NMC ModBus/JBus, Contact/Serial
Port Remote Power off (RJ11), 5 output contact (DB9), setup using Solution-Pac(8) (USB and DB9-serial port), EXB module
detection (RJ45), paralleling (DB 15)
Operating condition, standard and approval
Performance, safety, EMC, surge
protection
IEC/EN 62 040-3, IEC/EN 62 040-1-1, IEC/EN 62 040-2 class A (class B as option), 4 kV IEC 61 643, UL
1778 and CSA 22.2
(9)
Operating temperature, noise, approval 0°C to 40°C continuous, 45 dbA(10) , UL, TüV, GS mark, CB, C-Tick, CE, IEC 61 931
Dimension (HxWxD in mm) / Weight (kg)
MX RT standard
backup tower
444.5x130.6x735 / 57 kg Tower 690 (795 mm casters) x444.5x735 / 250 kg
Rack 16U x 444.5, compatible with 800-1000 mm deep rack
MX RT standard
backup rack
3Ux444.5 compatible with 800-1000
mm deep rack
Tower 690 (795 mm casters) x444.5x735 / 250 kg
Rack 16U x 444.5, compatible with 800-1000 mm deep rack
MX EXB battery unit
tower / rack
444.5x130.6x650 / 3U x 444.5 /
70 kg
dimension same as MX Frame / 194 kg for 15 kVA, 239 kg for 20 kVA
MX ModularEasy, paralleling kit dimension same as EXB battery
unit / 10kg
/ /
Part number
Convertible Tower/Rack
68504 68513 68514
EXB 68515 / /
1: 2 MXs can be paralleled using ModularEasy.
2: At 70% load.
3: 4 IEC C13 (10A) 2 m long cables for use with retention clips (8 cables for use with MX Frame).
4: Frequency conversion for non-paralleled units only.
5: Economy mode, 91% in normal mode.
6: At 70% nominal rating with power factor 0.7 typical values after 3 charge/discharge cycles, with 3-5
year old batteries. Weekly battery test without interrupting the load (daily or monthly if required). EXB
compatible with 0.8 power factor loads.
7: With MX Frame EXB (4 battery units).
8: Solution-Pac CD-ROM supplied as standard.
9: Applicable to US models.
10: 50 dbA above 5 kVA.