Datasheet

19
1: Maximum rating with EXB battery units: EX 1000 = 800 W, EX 1500 =1200 W. EX 3000 = 2400 W
2: Lower limits for <20%, <33%, <66%, >=66% of nominal power (VA). For active output power greater than 0.7 and 0.8 nominal rating, the lower limit is 180V and 190V respectively.
3:Derated by 15% when used as a frequency converter.
4: USB and RS232 serial ports cannot be used simultaneously.
TECHNICAL SPECIFICATION 1000 - 1000 RT2U 1500 - 1500 RT2U 2000 3000
Rating (VA / Watt)
1000 VA / 900 W
(1)
1500 VA / 1350 W
(1)
2200 VA / 1980 W 3000 VA / 2700 W
(1)
Technology Online double conversion Online double conversion Online double conversion Online double conversion
Format Mini tower or RT2U (tower/rack 2U) RT2U (tower / rack 2U) RT2U (tower / rack 2U)
Characteristic
Architecture Online double conversion with automatic by-pass and power factor correction
Input voltage and frequency range without
using battery
100/120/140/160 V
(2)
to 284V - 40 to 70 Hz 100/120/140/160 V
(2)
to 284V - 40 to 70 Hz
Output voltage and frequency 230V (adjustable to 200/208/220/240/250 V), 50/60 Hz auto-select or frequency converter mode
(3)
Connection
Input
1 IEC C14 (10A) socket 1 IEC C14 (10A) socket 1 IEC C20 (16A) or terminal block on HotSwap MBP
Hard-Wired
Output
6 IEC C13 (10A) socket 6 IEC C13 (10A) socket 8 IEC C13 (10A) socket + 1 IEC C19 (16A) socket
Remotely controlled Powershare socket 2 independent groups: 2 + 1 IEC C13 (10A) socket 2 groups of 2 x IEC C13 (10A)
Outputs with HotSwap MBP 6 IEC 10A socket or terminal blocks (HW version) or 3 BS socket
Outputs with FlexPDU 12 IEC 10A socket 12 IEC 10A socket 12 IEC 10A socket 12 IEC 10A socket
Battery
Typical backup times for 50 and 70% load
EX (min) 18/12 13/9 17/12 15/10
EX + 1 EXB (min) 75/50 50/35 85/60 60/40
EX + 4 EXB (min) 250/200 180/120 285/200 190/150
Battery management
Automatic weekly test (period adjustable using LCD display or in software supplied), automatic recognition of external
battery unit => continuous maximisation of backup time + deep discharge protection
Interface
Indicators and display 3 LEDS + adjustable multilingual display: display of measurement, access to control and set-up menu
Communication port 1 USB port + 1 RS232 serial port and relay contact
(4)
+ 1 mini terminal block for remote ON/OFF and emergency stop
Communications slot 1 slot for NMC Minislot card or NMC ModBus/JBus or MC Contact/Serial
Operating condition, standard and approval
Operating temperature noise level 0°C to 40°C continuous, 45 dBA 0°C to 40°C continuous, 45 dBA
Performance - Safety - EMC IEC/EN 62 040-3 (VFI-SS-113), IEC/EN 62 040-1-1, IEC/EN 60 950-1 (RD), IEC/EN 62 040-2 C1 Class
Approval CE, TüV GS, CB report, cTüV-US CE, TüV GS, CB report, cTüV-US
Dimension (HxWxD in mm) / Weight (kg)
Tower 440x242x153 / 15 kg 490x242x153 / 18 kg 640x86x440 (2U) / 31kg
490x131x440 (3U) / 30 kg
640x86x440 (2U) / 31kg
490x131x440 (3U) / 30 kg
Rack 86.5x438x483 86.5x438x483 86x440x640
131x440x490
88x440x640
131x440x490
Tower EXB 440x242x153 / 21 kg 440x242x153 / 21 kg 490x131x440 (3U) / 42 kg 490x131x440 (3U) / 42 kg
Rack EXB 483x86.5x438 (2U) / 24.5 kg 483x86.5x438 (2U) / 24.5 kg 490x131x440 (3U) / 42 kg 490x131x440 (3U) / 42 kg
Part Number
Tower 68181 68183 68401 68403
Rack 68182 68184 68401 68403
EXB 68185 68185 68405 68405