TECHNICAL SPECIFICATION 1250 2500 3000
Rating (VA / Watt) 1250 VA / 1150 W 2500 VA / 2250 W 3000 VA / 2700 W
Format RT2U (tower / rack 2U) RT2U (tower / rack 2U) RT2U (tower/rack 3U)
Characteristic
Technology Line-Interactive High Frequency (Booster + Fader)
Input voltage and frequency range without
using battery
160V-294V (adjustable to 150V-294V) 47 to 70 Hz (50 Hz system), 56.5 to 70 Hz (60 Hz system), up to 40 Hz in low-
sensitivity mode (programmable using Personal Solution-Pac software.
Output voltage and frequency 230 V (+6/-10 %) (Adjustable to 200 V (10 % derating of output power) / 208 V / 220 V / 230 V / 240 V),
50/60 Hz +/- 0.1 %
Connection
Input 1 IEC C14 (10 A) socket 1 IEC C20 (16 A) socket 1 IEC C20 (16 A) socket
Output 8 IEC C13 (10 A) 8 IEC C13 (10 A) socket
1 IEC C19 (16 A) socket
8 IEC C13 (10 A) socket
1 IEC C19 (16 A) socket
Remotely controlled socket 2 groups of 2 x IEC C13 (10 A) 2 groups of 2 x IEC C13 (10 A) 2 groups of 2 x IEC C13 (10 A)
Additional outputs with HS MBP 3 BS socket or 6 IEC 10 A socket or terminal blocks (HW version)
Additional outputs with FlexPDU 6 BS socket or 12 IEC 10 A socket
Battery
Typical backup times for 50 and 70% load*
Evolution S (min)
Evolution S + 1 EXB (min)
Evolution S + 4 EXB (min)
20/14
105/60
300/200
17/11
85/55
290/200
15/10
60/42
210/135
Battery management Automatic weekly test (period adjustable), automatic recognition of external battery units => continuous maximisation
of backup time + deep discharge protection
Interface
Communication port 1 USB port + 1 RS232 serial port and relay contact (USB and RS232 port cannot be used simultaneously) + 1 mini ter-
minal block for remote ON/OFF and Remote Power Off
Communications card slot 1 slot for NMC Minislot card (included in Netpack versions) or NMC ModBus/JBus or MC Contact/Serial
Operating condition, standard and approval
Operating temperature 0 to 40°C 0 to 40°C 0 to 40°C
Noise level < 45 dBA < 50 dBA < 50 dBA
Performance - Safety - EMC IEC/EN 62040-1-1 (Safety), IEC/EN 62040-2 EN 50091-2 class B (EMC), IEC/EN 62040-3 (Performance), IEC/EN 61000-
4-2, 61000-4-3, 61000-4-4; 61000-4-5, 61000-4-6, 61000-4-8 (EMI)
Approval CE, CB report, TÜV CE, CB report, TÜV CE, CB report, TÜV
Dimension (HxWxD in mm) / Weight (kg)
Dimension 86.2x440x509 (2U) 86.2x440x634 (RT2U)
130.7x440 x484 (RT3U)
86.2x440x634 (RT2U)
130.7x440 x484 (RT3U)
Weight of the Tower/Rack 24.3 33.8 33.8 (RT2U) - 34.3 (RT3U)
Dimension of EXB See UPS See UPS See UPS
Weight of the EXB 30.4 41.7 41.7
Part Number
Convertible Tower/Rack 68456 68461 68462
EXB Model 68470 68471 68471
* Runtimes are shown at 0.7 power factor. Backup times are approximate and may vary with equipment, configuration, battery age, temperature, etc.