Summary of power management
functions
Individual workstations
Personal Solution-Pac*
* Personal Solution-Pac is included with the UPS and is available from the Web site www.mgeups.com
* For advanced supervision of three-phase UPS and SSL, use the XML-Web card.
The servers are protected using the same Shutdown Modules.
6
Windows Mac OS 9/OS X Linux IBM AIX 4.3, 5.1, 5.2 Novell Netware
Server 2003/XP/2000 Sun Solaris WS 7,8, 9 4.1x, 5.x, 6
versions NT/9X PC 2.6, 7, 8
HP HP-UX 10.x, 11
Installation
Connection USB or RS232 USB RS232 RS232 RS232
(USB with NUT
Open-Source drivers)
Simple installation yes, “plug and play” yes yes yes yes
Basic functions
Automatic shutdown at yes yes yes yes -
end of back-up time (+ hibernation)
Automatic re-start yes yes yes yes yes
Alarm messages yes yes yes yes yes
Log file yes yes yes yes yes
Alarm messages by e-mail yes (+ pager et SMS) - yes yes -
GUI
User interface advanced basic semi graphic semi graphic Windows workstation
Graphic display of log file yes - - - -
Contextual help yes - - - -
Advanced functions
Automatic execution
of scripts yes yes yes yes yes
Event and action yes - yes yes yes
configurations
ON/OFF programming yes - - - -
Powershare
TM
outlet yes - - - yes
management
Solution Solution
“Network Management Card” * “Network Management Proxy”
UPS compatibility
Minislot for Pulsar Evolution and EXtreme C Connection to a Proxy system
Transverse for EXtreme, EX RT, Galaxy 3000, Windows NT/2000/XP for USB or RS232
Galaxy PW and MultiSlot
Network interface 10Base-T, 100Base-Tx not applicable
Network protocols TCP/IP, UDP,HTTP1.1, SNMPV1, Telnet, not applicable
TFTP, SMTP, BOOTP, DHCP / SNMP, XML, HTTP, HTTPS
SNMP traps yes, with acknowledgement yes -
MIB IETF MIB, standard MIB II, MGE MIB IETF MIB, standard MIB II, MGE MIB
Multi-server “shutdown” with different OS 50 (Shutdown Modules) unlimited - tested with more than 250 clients
Alarms by e-mail / pager / SMS yes -
Export logs yes yes (local)
Integral real time clock yes yes (proxy system clock)
Remote control of UPS / Powershare
TM
yes -
Settings / Maintenance Local (RS232) or remote (HTTP or Telnet) Local or remote (HTTP/HTTPS)
Simulation of shutdown yes yes
Environment measurements (temperature, humidity, contacts) yes, with Environment sensor -
e-Teleservice support yes -
Connection to IP networks
Network applications