Datasheet

Page 4 - 51029398EN/AD
Characteristics
Basic mode pin-out
Pin 1: not used,
Pin 2: Battery fault,
Pin 3: Remote Power Off signal,
Pin 4: Operation on mains
(not on battery),
Pin 5: User common,
Pin 6: Operation on automatic by-pass,
Pin 7: Low battery,
Pin 8: Load protected,
Pin 9: Operation on battery.
When the status is active, the contact
between the common (Pin 5) and the
relevant information pin is closed (Fig. 3).
Remote Power Off
mode pin-out
Pin 1: not used,
Pin 2: not used,
Pin 3: Remote Power Off contact,
Pin 4: not used,
Pin 5: Communication card common,
Pin 6: not used,
Pin 7: not used,
Pin 8: not used,
Pin 9: not used.
Fig. 3
Output relays
specifications
Voltage: 40V AC, 60 V DC
Current: 2 A
Power: 62,5 VA, 30 W
Example: for 48 V DC, Imax=625 mA
Remote Power Off
Signal:
activation voltage: 5 V DC to 27 V DC
current: 10 mA max
Contact:
switched over voltage: 5 VDC
loop current: 2 mA
n.c.
common
5432
9876
1
n.o. n.o. n.o. n.o. n.o.