Page 2 - 51029066EN/BB
Introduction Thank you for selecting an MGE UPS SYSTEMS product to protect your electrical equipment. The JBUS/MODBUS card has been designed with the utmost care. We recommend that you take the time to read this manual to take full advantage of the many features of your new equipment. A lot of information about MGE UPS SYSTEMS products are available on our Web site www.mgeups.com.
Foreword Federal Communication Commission (FCC) statement This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment.
Contents 1. Presentation 1.1 1.2 1.3 1.4 2. Installation 2.1 2.2 2.3 2.4 2.5 3. Unpacking and checking contents ................................................................................................................ 6 Overview ........................................................................................................................................................... 7 Functions .......................................................................................................
1. Presentation 1.1 Unpacking and checking contents www.mgeups.com MGE UPS SYSTEMS "JBUS/MODBUS" communication card Installation and user manual JBUS/MODBUS 66061 THE UNINTERRUPTIBLE POWER PROVIDER JBUS/MODBUS JBUS/MODBUS 66061 Page 6 - 51029066EN/BB The product is made up of the following elements: ◗ JBUS/MODBUS communication card. ◗ A front plate specially designed for Galaxy PW UPSs (Uninterruptible Power Supply). ◗ Installation and user manual.
1. Presentation 1.2 Overview 1 Switches for RS485 settings (SA2). 2 Switches for JBUS/MODBUS settings (SA1). 3 RS232 link configuration jumpers. 4 RS485 communication port. 5 RS232 communication port. 6 Diagnostic LED. 7 Card restart push button.
1. Presentation 1.3 Functions The JBUS/MODBUS communication card provides UPS (Uninterruptible Power Supply) and STS (Static Transfer Switch) data (states and measures) to be sent a computer system. The JBUS hexadecimal (MODBUS RTU) communication protocol is used in slave mode. The system provides a communication channel with an RS485 or RS232 interface. Note: The JBUS/MODBUS communication card may be used in all UPSs and STSs equipped with UPS BUS communication slots.
1. Presentation JBUS Protocol Detailed description of the JBUS/MODBUS protocol is available on our Web site www.mgeups.com The standard JBUS/MODBUS functions provided by the card are: ◗ function 3 : read n words, ◗ function 5 : write 1 bit, ◗ function 6 : write 1 word, ◗ function 16 : write n words. The data (states or measures) are stored in a sequencial way in the JBUS/MODBUS tables.
2. Installation 2.1 Configuration of the JBUS/MODBUS communication parameters If needed, it is possible to modify the default values of the JBUS/MODBUS communication parameters, following the actions below: 1 - Place all the SA1 switches to the ON position. 1 J3 JMP1 JMP2 SA1 RS232 SA1 OFF ON 8 J4 2 - Connect the RS232 link to a terminal (Microsoft Hyper terminal).
2. Installation 3 - Set the terminal with the following communication parameters: 9600 baud rate, even parity, 1 stop bit and 7 data bits. 4 - Press the push button 7 more than 3 seconds on the card. 5 - Configuration mode is operational. Check that the diagnostic LED 6 is blinking regularly twice per seconds. A command prompt CDE-> is displayed on the terminal screen. 6 - Enter the configuration command you need (see table below). Enter a carriage return ↵ after each command.
2. Installation 2.2 Return to the default JBUS/MODBUS parameters To return to the default parameters (see §1.4) of the JBUS/MODBUS communication, you must: 1 - Place all the SA1 switches to the OFF position. 1 J3 JMP1 JMP2 SA1 RS232 SA1 RS485 7 SA2 J4 OFF ON 8 2 - Press the push button 7 more than 3 seconds on the card. 3 - Release the button and restart the board by pressing the push button less than 3 seconds.
2. Installation JMP1 JMP2 2.
2. Installation 2.4 RS485 link configuration and connection For proper operation, the polarity of EIA RS485 2-wire and 4-wire lines must be set at only one point and the lines terminated at the end. Polarity Normally, the master of the network sets the polarity of the line (Rp resistor). Termination The two ends of the line must be terminated (Ra resistor). Allow for 1 or 2 terminators to avoid mismatching the line when any equipment at the end of the line is disconnected.
2. Installation SA2 switches are used to make the termination and the polarity of the RS485 link: SA2 1 (all to OFF position) J3 JMP1 JMP2 SA1 RS232 OFF ON 8 2 wires connection.
2.
2. Installation Card settings of an intermediate cubicle in 2 wires Link without polarity and without termination. ON J4 OFF 87654321 SA2 Card settings of an end of line cubicle in 2 wires Link without polarity and with termination. ON J4 87654321 OFF SA2 Others settings in 2 wires Link with polarity and with termination. Link with polarity and without termination.
2.
2. Installation Card settings of an intermédiate cubicle in 4 wires Link without polarity and without termination. ON J4 OFF 87654321 SA2 Card settings of an end of line cubicle in 4 wires Link without polarity and with termination. ON J4 OFF 87654321 SA2 Others settings in 4 wires Link with polarity and with termination. Link with polarity and without termination.
2. Installation 2.5 Card installation It is not necessary to turn the UPS or the STS off. ASI 1. Using a screwdriver, remove the cover from a free slot in the UPS or in the STS. 2. Insert and secure the JBUS/MODBUS communication card in the UPS or in the STS.
3. Operation The JBUS/MODBUS communication card can be inserted in all products equipped with communication slots. For each of these products, data available through the JBUS/MODBUS protocol are listed in the tables below. 3.
3.
3. Operation 3.
3.
3.
3. Operation 3.
3.
3.
3. Operation Description of the physical quantity Word Unit Nominal backup time Battery backup time Battery room temperature Battery charging level Battery recharge duration 148 149 14A 14B 14F mn mn °C % mn 3.4 In Upsilon STS In addition to the tables of data (states and measures) available for reading, there is a table for writing commands.
3.
3.
4. Troubleshooting Problem Page 32 - 51029066EN/BB Probable cause Remedy The diagnostic LED 6 remains always OFF. The card is not supplied with power. - Check that the card is correctly inserted and secured in its slot, - Check that the system is energised, - Remove the card and install it again. The diagnostic LED 6 remains always ON. The card is blocked. - Check that the push button 7 is released (not pressed), - Remove the card and install it again. JBUS/RS232 communication is not operational.
5. Index A R Line termination ........................................................ 14-19 2 wire connection ................................................ 15-17, 19 4 wire connection ................................................ 15, 18-19 Data transmit .................................................................. 13 Data receive ............................................................. 16, 18 Recycling .........................................................................
Page 34 - 51029066EN/BB
www.mgeups.
Page 2 - 51029066FR/BB
Introduction Nous vous remercions d’avoir choisi les produits MGE UPS SYSTEMS pour la sécurité de vos équipements. La carte JBUS/MODBUS a été élaborée avec le plus grand soin. Pour exploiter au maximum ses performances, nous vous conseillons de prendre le temps d’étudier ce manuel. Consulter notre site web www.mgeups.com sur lequel sont disponibles diverses informations sur les produits de communication MGE UPS SYSTEMS.
Avant propos Conventions utilisées dans ce manuel Suivre impérativement ces consignes. Informations et conseils. Signalisation visuelle. Action.
Sommaire 1. Présentation 1.1 1.2 1.3 1.4 2. Installation 2.1 2.2 2.3 2.4 2.5 3. Déballage et vérification du contenu ............................................................................................................. 6 Vue d’ensemble ............................................................................................................................................... 7 Fonctions ...........................................................................................................
1. Présentation 1.1 Déballage et vérification du contenu www.mgeups.com MGE UPS SYSTEMS "JBUS/MODBUS" communication card Installation and user manual JBUS/MODBUS 66061 THE UNINTERRUPTIBLE POWER PROVIDER JBUS/MODBUS JBUS/MODBUS 66061 Page 6 - 51029066FR/BB Le produit que vous venez d'acquérir se compose des éléments suivants : ◗ Une carte de communication JBUS/MODBUS. ◗ Une face avant spécifique aux ASI (Alimentation Sans Interruption) de type Galaxy PW.
1. Présentation 1.2 Vue d’ensemble 1 Boîtier de configuration de la liaison RS485 (SA2). 2 Boîtier de paramétrage de la communication JBUS/MODBUS (SA1). 3 Cavaliers de configuration de la liaison RS232. 4 Port de communication RS485. 5 Port de communication RS232. 6 Voyant de diagnostic. 7 Bouton poussoir de redémarrage de la carte.
1. Présentation 1.3 Fonctions La carte de communication JBUS/MODBUS permet la transmission à un outil informatique d’un ensemble d’informations concernant l’état de fonctionnement de l’ASI (Alimentation Sans Interruption) ou du STS (Système de Transfert Statique) dans lequel elle est insérée. Le protocole de communication employé est JBUS hexadécimal (MODBUS RTU) en mode esclave. Le système offre une voie de communication équipée au choix d’une jonction RS485 ou d’une jonction RS232.
1. Présentation Protocole JBUS La description détaillée du protocole JBUS/MODBUS est disponible sur notre site www.mgeups.com Les fonctions JBUS/MODBUS standards qui sont implémentées dans la carte sont : ◗ fonction 3 : lecture de n mots, ◗ fonction 5 : écriture de 1 bit, ◗ fonction 6 : écriture de 1 mot, ◗ fonction 16 : écriture de n mots. Les données (états et mesures) sont rangées de manière contiguë dans les tables JBUS/MODBUS.
2. Installation 2.1 Configuration des paramètres de communication JBUS/MODBUS Si les valeurs par défaut (voir §1.4) des paramètres de communication JBUS/MODBUS ne conviennent pas, il est possible de les modifier en suivant la procédure suivante : 1 - Placer tous les interrupteurs du boîtier SA1 en position ON. 1 J3 JMP1 JMP2 SA1 RS232 SA1 8 J4 2 - Connecter la liaison RS232 de la carte à un terminal (Microsoft Hyper terminal).
2. Installation 3 - Régler le terminal avec les paramètres de communication suivants : 9600 bauds, parité paire, 1 bit stop et 7 bits de données. 4 - Appuyer pendant plus de 3 secondes sur le bouton poussoir 7 de la carte. 5 - Le mode de configuration est actif. Vérifier que le voyant de diagnostic 6 clignote régulièrement deux fois par secondes. Une invite CDE-> s’affiche sur l’écran du terminal. 6 - Taper les commandes de paramétrage souhaitées (voir tableau ci-dessous).
2. Installation 2.2 Retour aux paramètres JBUS/MODBUS par défaut Pour revenir aux paramètres par défaut (voir §1.4) de communication JBUS/MODBUS, il faut : 1 - Placer tous les interrupteurs du boîtier SA1 en position OFF. 1 J3 JMP1 JMP2 SA1 RS232 SA1 RS485 7 SA2 J4 OFF ON 8 2 - Appuyer pendant plus de 3 secondes sur le bouton poussoir 7 de la carte. 3 - Relâcher le bouton et redémarrer la carte en appuyant un coup bref (pendant moins de 3 secondes) sur le bouton poussoir.
2. Installation JMP1 JMP2 2.
2. Installation 2.4 Configuration et raccordement de la liaison RS485 La liaison EIA RS485, en 2 fils ou en 4 fils, doit être polarisée en un point unique de la ligne et adaptée aux deux extrémités de cette ligne pour un fonctionnement correct. Polarisation L’usage et la logique veulent que l’équipement maître du réseau polarise la ligne (résistances Rp). Adaptation L’adaptation (résistances Ra) doit être réalisée aux deux extrémités de la ligne.
2. Installation Le boîtier SA2 est utilisé pour réaliser l'adaptation et la polarisation de la liaison RS485 : SA2 1 (tous sur OFF) J3 JMP1 JMP2 SA1 RS232 OFF ON 8 Raccordement en 2 fils.
2.
2. Installation Configuration de la carte d'un équipement intermédiaire en 2 fils Liaison sans polarisation et sans adaptation. ON J4 OFF 87654321 SA2 Configuration de la carte d'un équipement de bout de ligne en 2 fils Liaison sans polarisation et avec adaptation. ON J4 OFF 87654321 SA2 Autres configurations en 2 fils Liaison avec polarisation et avec adaptation. Liaison avec polarisation et sans adaptation.
2.
2. Installation Configuration de la carte d'un équipement intermédiaire en 4 fils Liaison sans polarisation et sans adaptation. ON J4 OFF 87654321 SA2 Configuration de la carte d'un équipement de bout de ligne en 4 fils Liaison sans polarisation et avec adaptation. ON J4 OFF 87654321 SA2 Autres configurations en 4 fils Liaison avec polarisation et avec adaptation. Liaison avec polarisation et sans adaptation.
2. Installation 2.5 Mise en place Il n’est pas nécessaire de mettre l’ASI ou le STS hors-tension. ASI 1. Dévisser et ôter le plastron d’un emplacement disponible de l’ASI ou du STS, 2. Insérer et fixer la carte de communication JBUS/MODBUS dans l’ASI ou dans le STS.
3. Utilisation La carte de communication JBUS/MODBUS peut être insérée dans tous les produits équipés de slots de communication. Les tables de données accessibles via le protocole JBUS sont présentées pour chacun de ces produits. Les adresses JBUS sont exprimées en hexadécimal. 3.
3.
3. Utilisation 3.
3.
3.
3. Utilisation 3.
3.
3.
3. Utilisation Description de la grandeur physique Mot Unité Autonomie nominale Autonomie batterie Température local batterie Taux de charge batterie Temps de recharge batterie 148 149 14A 14B 14F mn mn °C % mn 3.4 Dans Upsilon STS En plus des tables des états et mesures accessibles en lecture, une table de commandes est disponible en écriture.
3.
3.
4. Maintenance Problème Page 32 - 51029066FR/BB Diagnostic Résolution Le voyant de diagnostic 6 reste éteint en permanence. La carte n’est pas alimentée. - Vérifier que la carte est correctement insérée dans son emplacement, - Vérifier que le système est sous-tension, - Enlever la carte puis l’insérer de nouveau. Le voyant de diagnostic 6 reste allumé en permanence. La carte est bloquée.
5. Index A R Adaptation de la ligne ............................................... 14-19 Raccordement en 2 fils ....................................... 15-17, 19 Raccordement en 4 fils ....................................... 15, 18-19 Réception de données ................................................... 13 Réception d'informations .......................................... 16, 18 Recyclage ........................................................................
Page 34 - 51029066FR/BB