Datasheet

10
Technical Data 10164
Effective September 2015
Bussmann series
500 Volts gG/gL NH Fuse links
EATON www.eaton.com
Time-current curves - NH Size 02
Technical data - NH size 02
Part numbers
with metal
gripping lugs
Part numbers
with insulated
metal gripping
lugs
Fuse link
size
Rated
current
(Amps)
Rated
voltage
(V a.c.)
I
2
t (Amps
2
Seconds)
Watts loss
Net weight
per fuse
(kg)
Minimum
pre-arcing
*I
1
120kA
at 500 V a.c.
35NHG02B 35NHG02BI 02 35 500 2400 11,800 4.7 0.40
40NHG02B 40NHG02BI 40 3300 16,500 5
50NHG02B 50NHG02BI 50 5600 27,800 6.4
63NHG02B 63NHG02BI 63 6600 26,100 5.5
80NHG02B 80NHG02BI 80 9800 38,900 7.3
100NHG02B 100NHG02BI 100 20,600 82,300 7.5
125NHG02B 125NHG02BI 125 25,000 100,000 12
160NHG02B 160NHG02BI 160 62,000 248,000 12
200NHG02B 200NHG02BI 200 96,900 367,900 15
224NHG02B 224NHG02BI 224 124,000 471,200 18
250NHG02B 250NHG02BI 250 151,300 574,900 19
*I
1
is the maximum breaking capacity test at rated voltage according to IEC 60269 requirements
Time in seconds (s)
Time in seconds (s)
Current in Amps (A)
Current in Amps (A)