Datasheet

Table Of Contents
Graphical LCD Internal battery type
LEDs
Topology Battery replacement
Diagnostics
Transfer time Battery runtime
ROO/RPO
Rail kit/tower stand
Nominal voltage Start-on-battery
Voltage range
Serial port
Frequency USB port
Frequency range
Optional
communications
Cables
Power draw of UPS
(full load)
Power management
software
Safety markings
Safety conformance
Power factor 0.9+ EMC compliance
On utility voltage regulation 120V: 102–132 Vac
Operating
temperature
208V: 177–229 Vac Storage temperature
230V: 184–265 Vac Relative humidity
On battery voltage -10%, +6% of nominal Surge suppression
Efficiency Audible noise
Altitude
Frequency regulation
Over current protection
5PX UPS model Line mode, BTUs/hr Battery mode, BTUs/hr
1000 VA 305 2047
1500 VA 305 2047
2200 VA 305 2047
3000 VA 305 2047
Eaton 5PX UPS
Technical Specifications
On battery: 70% (1000–1750 VA)
75% (2200–3000 VA)
General
Electrical input
Electrical output
Environmental
Communications
Battery
Included with all units
Normal or line mode: >94%
Heat dissipation table 0.1 Hz
Electronic current limit
Two groups of two controlled outlets
1500: 12.50A @120V
2200: 16.25A @120V
3000: 25.4A @120V, 14.4 @ 208V
50/60 Hz
47–70 Hz for 50 Hz operation
56.5–70 Hz for 60 Hz operation
1000: 8.33A @120V
100/120/127/200/208/220/230/240 V
120V: 89–151 Vac
208V: 160–263 Vac
230V: 160–294 Vac
Up to 10,000 ft (3000M) without de-rating
120V: UL 1778; UL497A; cUL
230V: IEC/EN 62040-1-1; IEC/EN 62040-3
120V: FCC Part 15 subpart B Class A
230V: IEC/EN 32010-2
0˚C (32˚F) to +40˚C (104˚F)
-15˚C (5˚F) to +50˚C (122˚F)
Load segments
Allows start of UPS without utility input
RS-232 (RJ45) ports
As standard (HID)
ConnectUPS-MS Network
Management Card
RS-232 and USB 6-foot communications
Intelligent Power
®
Software Suite
20–95% non-condensing
ANSI C62.41 Category A (formerly IEEE 587)
1kVA - 2.5kVA: < 45 dBA
3kVA: < 50dBA
120V: UL; cUL, NOM
230V: CE, CB report, TÜV
2200 VA: 3 min w/internal batteries @1760W load
3000 VA: 4 min w/internal batteries @2400W load
Hot-swappable internal batteries
Sealed, lead-acid; maintenance freeGraphical display. UPS Status in a single view.
1500 VA: 5 min w/internal batteries @1200W load
1000 VA: 9 min w/internal batteries @800W load
3 status-indicating LEDs
Full system self-test at power up
Rear deck emergency stop connector (for
remote on/off and power off)
1–4 ms typical
Line-interactive