Datasheet

8
Technical Data 10164
Effective September 2015
Bussmann series
500 Volts gG/gL NH Fuse links
EATON www.eaton.com
Time-current curves - NH Size 01
TIME (Seconds)
CURRENT (Amperes)
68422648 24
10
100 1000
2
6
4
0.1
0.01
1
6
4
2
6
2
4
10
100
6
4
2
6
4
2
6
4
2
1 000
10 000
32
35
40
50
63
80
100
125
160
16
10
20
25
864
6
Technical data - NH size 01
Part numbers
with metal
gripping lugs
Part numbers
with insulated
metal gripping
lugs
Fuse link
size
Rated
current
(Amps)
Rated
voltage
(V a.c.)
I
2
t (Amps
2
Seconds)
Watts loss
Net weight
per fuse
(kg)
Minimum
pre-arcing
*I
1
120kA
at 500 V a.c.
6NHG01B 6NHG01BI 01 6 500 14 21 2 0.27
10NHG01B 10NHG01BI 10 58 290 2
16NHG01B 16NHG01BI 16 240 1200 3
20NHG01B 20NHG01BI 20 490 2500 3.4
25NHG01B 25NHG01BI 25 1200 5600 5
32NHG01B 32NHG01BI 32 1800 9000 4.8
35NHG01B 35NHG01BI 35 2400 11,800 4.6
40NHG01B 40NHG01BI 40 3300 16,500 5
50NHG01B 50NHG01BI 50 5600 27,800 6.3
63NHG01B 63NHG01BI 63 6600 26,100 5.6
80NHG01B 80NHG01BI 80 9800 38,900 7.1
100NHG01B 100NHG01BI 100 20,600 82,300 7.7
125NHG01B 125NHG01BI 125 25,000 125,000 11.8
160NHG01B 160NHG01BI 160 62,000 310,000 12.3
*I
1
is the maximum breaking capacity test at rated voltage according to IEC 60269 requirements