Data Sheet

Solid or stranded AWG 3/0
Terminal screw M10
Tightening torque Nm 10
Stripping length mm 24
Tools
Hexagon socket-head spanner SW mm 5
Auxiliary and control circuits
Rated impulse withstand voltage U
imp
V 4000
Overvoltage category/pollution degree III/3
Terminal capacities
mm
2
Solid
mm
2
1 x (0.75 - 4)
2 x (0.75 - 4)
Flexible with ferrule
mm
2
1 x (0.75 - 2.5)
2 x (0.75 - 2.5)
Solid or stranded AWG 2 x (18 - 14)
Terminal screw M3.5
Tightening torque Nm 1.2
Stripping length mm 8
Tools
Pozidriv screwdriver Size 2
Standard screwdriver mm 1 x 6
Rated insulation voltage U
i
V AC 500
Rated operational voltage U
e
V AC 500
Safe isolation to EN 61140
between the auxiliary contacts V AC 240
Conventional thermal current I
th
A 6
Rated operational current I
e
A
AC-15
Make contact
120 V I
e
A 1.5
220 V 230 V 240 V I
e
A 1.5
380 V 400 V 415 V I
e
A 0.5
500 V I
e
A 0.5
Break contact
120 V I
e
A 1.5
220 V 230 V 240 V I
e
A 1.5
380 V 400 V 415 V I
e
A 0.9
500 V I
e
A 0.8
DC L/R ≦ 15 ms
Switch-on and switch-off conditions based on DC-13, time constant as specified.
24 V I
e
A 0.9
60 V I
e
A 0.75
110 V I
e
A 0.4
220 V I
e
A 0.2
Short-circuit rating without welding
max. fuse A gG/gL 6
Notes
Notes Ambient air temperature: Operating range to IEC/EN 60947, PTB: -5°C to +55°C
Main circuits terminal capacity solid and flexible conductors with ferrules: When using 2 conductors use equal cross-sections.
Rating data for approved types
Auxiliary contacts
Pilot Duty
AC operated B300 at opposite polarity
B600 at same polarity
DC operated R300
Short Circuit Current Rating SCCR
06/16/2021 Eaton 278464 ED2021 V80.0 EN 3 / 7