Data Sheet
Terminal capacities
mm
2
Screw terminals
Solid
mm
2
1 x (0.75 - 2.5)
2 x (0.75 - 2.5)
Flexible with ferrule
mm
2
1 x (0.75 - 2.5)
2 x (0.75 - 2.5)
Solid or stranded AWG 18 – 14
Pozidriv screwdriver Size 2
Standard screwdriver mm 0.8 x 5.5
1 x 6
Max. tightening torque Nm 1.2
Contacts
Interlocked opposing contacts within an auxiliary contact module (to IEC 60947-5-1
Annex L)
Yes
N/C contact (not late-break contact) suitable as a mirror contact (to IEC/EN
60947-4-1 Annex F)
DILM40 - DILM225A
Rated impulse withstand voltage U
imp
V AC 6000
Overvoltage category/pollution degree III/3
Rated insulation voltage U
i
V AC 690
Rated operational voltage U
e
V AC 500
Safe isolation to EN 61140
between coil and auxiliary contacts V AC 440
between the auxiliary contacts V AC 440
Between auxiliary contacts and main contacts V AC 440
Rated operational current A
Conventional free air thermal current, 1 pole
at 60 °C I
th
A 10
AC-15
220 V 230 V 240 V I
e
A 4
380 V 400 V 415 V I
e
A 4
500 V I
e
A 1.5
DC current
Switch-on and switch-off conditions based on DC-13, time constant as specified.
DC L/R ≦ 15 ms
Contacts in series: A
1 24 V A 10
1 60 V A 6
1 110 V A 3
1 220 V A 1
DC-13 (6xP)
24 V I
e
A 2
60 V I
e
A 1.5
110 V I
e
A 0.8
220 V I
e
A 0.3
Control circuit reliability Failure rate λ
<10
-8
, < one failure at 100 million operations
(at U
e
= 24 V DC, U
min
= 17 V, I
min
= 5.4 mA)
Short-circuit rating without welding
Short-circuit protection maximum fuse
500 V A gG/gL 16
Rated conditional short-circuit current 500 V I
q
kA 1
Current heat loss at I
th
AC operated W 0.69
DC operated W 0.69
Current heat loss per auxiliary circuit at I
e
(AC-15/230 V) CO 0.11
Rating data for approved types
Auxiliary contacts
Pilot Duty
06/18/2021 Eaton 278425 ED2021 V80.0 EN 2 / 4