Data Sheet

208 V
230 V
240 V
Hk 20
460 V
480 V
Hk 40
575 V
600 V
Hk 50
1-fase
115 V
120 V
Hk 3
230 V
240 V
Hk 10
Generell bruk A 80
Short Circuit Current Rating SCCR
Basic Rating
SCCR kA 10
maks. sikring A 250
maks.. CB A 250
480 V High feil
SCCR (sikring) kA 30/100
maks. sikring A 250/150 Class J
SCCR (CB) kA 65
maks.. CB A 100
600 V High Fault
SCCR (sikring) kA 30/100
maks. sikring A 250/150 Class J
SCCR (CB) kA 30
maks.. CB A 250
Special Purpose Ratings
Electrical Discharge Lamps (Ballast)
480V 60Hz 3-fase, 277V 60Hz 1-fase A 79
600V 60Hz 3-fase, 347V 60Hz 1-fase A 79
Incandescent Lamps (Tungsten)
480V 60Hz 3-fase, 277V 60Hz 1-fase A 74
600V 60Hz 3-fase, 347V 60Hz 1-fase A 74
Resistance Air Heating
480V 60Hz 3-fase, 277V 60Hz 1-fase A 79
600V 60Hz 3-fase, 347V 60Hz 1-fase A 79
Elevator ControlElevator Control
200V 60Hz 3phase Hk 10
200V 60Hz 3phase A 32.2
240V 60Hz 3phase Hk 15
240V 60Hz 3phase A 42
480V 60Hz 3phase Hk 30
480V 60Hz 3phase A 40
600V 60Hz 3phase Hk 40
600V 60Hz 3phase A 41
Data for konstruksjonsdokumentasjon iht. IEC/EN 61439
Tekniske data for konstruksjonsdokumentasjon
Nominell strøm for angivelse av tapseffekt I
n
A 50
Tapseffekt per pol, strømavhengig P
vid
W 3.3
Tapseffekt for driftsmiddelet, strømavhengig P
vid
W 9.9
Tapseffekt statisk, uavhengig av strøm P
vs
W 1
Avleveringskapasitet for tapseffekt P
ve
W 0
Omgivelsestemperatur ved drift min. °C -25
Omgivelsestemperatur ved drift maks. °C 60
18.06.2021 Eaton 278009 ED2021 V80.0 NO 5 / 7