Data Sheet

Sluittijd ms < 54
openingsvertraging ms
Uitschakeltijd ms < 24
Lichtboogtijd ms 10
Elektromagnetische compatibiliteit
Storingsemissie Conform EN 61131-1
Storingsongevoeligheid Conform EN 61131-1
Goedgekeurde vermogensspecificaties
Schakelvermogen
Max. motorvermogen
3-fase
200 V
208 V
HP 15
230 V
240 V
HP 20
460 V
480 V
HP 40
575 V
600 V
HP 50
1-fase
115 V
120 V
HP 3
230 V
240 V
HP 10
General use A 80
Short Circuit Current Rating SCCR
Basic Rating
SCCR kA 10
max. Fuse A 250
max. CB A 250
480 V High Fault
SCCR (zekering) kA 30/100
max. Fuse A 250/150 Class J
SCCR (CB) kA 65
max. CB A 100
600 V High Fault
SCCR (zekering) kA 30/100
max. Fuse A 250/150 Class J
SCCR (CB) kA 30
max. CB A 250
Special Purpose Ratings
Electrical Discharge Lamps (Ballast)
480V 60Hz 3fase, 277V 60Hz 1fase A 79
600V 60Hz 3fase, 347V 60Hz 1fase A 79
Incandescent Lamps (Tungsten)
480V 60Hz 3fase, 277V 60Hz 1fase A 74
600V 60Hz 3fase, 347V 60Hz 1fase A 74
Resistance Air Heating
480V 60Hz 3fase, 277V 60Hz 1fase A 79
600V 60Hz 3fase, 347V 60Hz 1fase A 79
Elevator Control
200V 60Hz 3fase HP 10
200V 60Hz 3fase A 32.2
240V 60Hz 3fase HP 15
240V 60Hz 3fase A 42
480V 60Hz 3fase HP 30
480V 60Hz 3fase A 40
600V 60Hz 3fase HP 40
17.06.2021 Eaton 278009 ED2021 V80.0 NL 5 / 13