Data Sheet

DATASHEET - DILM40(RDC24)
Contactor, 3 pole, 380 V 400 V 18.5 kW, RDC 24: 24 - 27 V DC, DC operation,
Screw terminals
Part no. DILM40(RDC24)
Catalog No. 277780
Alternate Catalog
No.
XTCE040D00TD
EL-Nummer
(Norway)
4130441
Delivery program
Product range Contactors
Application Contactors for Motors
Subrange Contactors up to 170 A, 3 pole
Utilization category AC-1: Non-inductive or slightly inductive loads, resistance furnaces
AC-3/AC-3e: Normal AC induction motors: Starting, switching off while running
AC-4: Normal AC induction motors: starting, plugging, reversing, inching
Notes Also suitable for motors with efficiency class IE3.
Connection technique Screw terminals
Number of poles 3 pole
Rated operational current
AC-3
Notes At maximum permissible ambient temperature (open.)
Also tested according to AC-3e.
380 V 400 V I
e
A 40
AC-1
Conventional free air thermal current, 3 pole, 50 - 60 Hz
Open
at 40 °C I
th
=I
e
A 60
enclosed I
th
A 45
Conventional free air thermal current, 1 pole
open I
th
A 125
enclosed I
th
A 112
Max. rating for three-phase motors, 50 - 60 Hz
AC-3
220 V 230 V P kW 12.5
380 V 400 V P kW 18.5
660 V 690 V P kW 23
AC-4
220 V 230 V P kW 5
380 V 400 V P kW 9
660 V 690 V P kW 12
Contact sequence
Instructions Contacts to EN 50 012.
integrated suppressor circuit in actuating electronics
Can be combined with auxiliary contact DILM150-XHI(V)…
DILM1000-XHI(V)…
Actuating voltage RDC 24: 24 - 27 V DC
Voltage AC/DC DC operation
Connection to SmartWire-DT no
Frame size 3
06/18/2021 Eaton 277780 ED2021 V80.0 EN 1 / 12