Data Sheet

DATASHEET - DILMC17-10(RDC24)
Contactor, 3 pole, 380 V 400 V 7.5 kW, 1 N/O, RDC 24: 24 - 27 V DC, DC
operation, Spring-loaded terminals
Part no. DILMC17-10(RDC24)
Catalog No. 277595
Alternate Catalog
No.
XTCEC018C10TD
EL-Nummer
(Norway)
4110317
Delivery program
Product range Contactors
Application Contactors for Motors
Subrange Contactors up to 170 A, 3 pole
Utilization category AC-1: Non-inductive or slightly inductive loads, resistance furnaces
AC-3/AC-3e: Normal AC induction motors: Starting, switching off while running
AC-4: Normal AC induction motors: starting, plugging, reversing, inching
Notes Also suitable for motors with efficiency class IE3.
Connection technique Spring-loaded terminals
Description Spring-cage terminals on auxiliary and control circuit terminals
Number of poles 3 pole
Rated operational current
AC-3
Notes At maximum permissible ambient temperature (open.)
Also tested according to AC-3e.
380 V 400 V I
e
A 18
AC-1
Conventional free air thermal current, 3 pole, 50 - 60 Hz
Open
at 40 °C I
th
=I
e
A 40
enclosed I
th
A 32
Conventional free air thermal current, 1 pole
open I
th
A 88
enclosed I
th
A 80
Max. rating for three-phase motors, 50 - 60 Hz
AC-3
220 V 230 V P kW 5
380 V 400 V P kW 7.5
660 V 690 V P kW 11
AC-4
220 V 230 V P kW 2.5
380 V 400 V P kW 4.5
660 V 690 V P kW 6.5
Contacts
N/O = Normally open 1 N/O
Contact sequence
Instructions Contacts to EN 50 012.
Auxiliary current, coil, and main current terminals with spring-cage connection
technology.
Main current connections with screw terminals.
integrated suppressor circuit in actuating electronics
Can be combined with auxiliary contact DILM32-XHIC…
DILA-XHIC(V)…
06/18/2021 Eaton 277595 ED2021 V80.0 EN 1 / 13