Data Sheet
DATASHEET - DILMC12-10(24VDC)
Contactor, 3 pole, 380 V 400 V 5.5 kW, 1 N/O, 24 V DC, DC operation,
Spring-loaded terminals
Part no. DILMC12-10(24VDC)
Catalog No. 277532
Alternate Catalog
No.
XTCEC012B10TD
EL-Nummer
(Norway)
4110311
Similar to illustration
Delivery program
Product range Contactors
Application Contactors for Motors
Subrange Contactors up to 170 A, 3 pole
Utilization category AC-1: Non-inductive or slightly inductive loads, resistance furnaces
AC-3/AC-3e: Normal AC induction motors: Starting, switching off while running
AC-4: Normal AC induction motors: starting, plugging, reversing, inching
Notes Also suitable for motors with efficiency class IE3.
Connection technique Spring-loaded terminals
Number of poles 3 pole
Rated operational current
AC-3
Notes At maximum permissible ambient temperature (open.)
Also tested according to AC-3e.
380 V 400 V I
e
A 12
AC-1
Conventional free air thermal current, 3 pole, 50 - 60 Hz
Open
at 40 °C I
th
=I
e
A 22
enclosed I
th
A 18
Conventional free air thermal current, 1 pole
open I
th
A 50
enclosed I
th
A 45
Max. rating for three-phase motors, 50 - 60 Hz
AC-3
220 V 230 V P kW 3.5
380 V 400 V P kW 5.5
660 V 690 V P kW 6.5
AC-4
220 V 230 V P kW 2
380 V 400 V P kW 3
660 V 690 V P kW 4.4
Contacts
N/O = Normally open 1 N/O
Contact sequence
Instructions Contacts to EN 50 012.
Auxiliary current, coil, and main current terminals with spring-cage connection
technology.
Integrated varistor suppressor circuit.
Can be combined with auxiliary contact DILM32-XHIC…
DILA-XHIC(V)…
06/18/2021 Eaton 277532 ED2021 V80.0 EN 1 / 13