Data Sheet
Flexible with ferrule
mm
2
1 x (0.75 - 1.5)
2 x (0.75 - 1.5)
Solid or stranded AWG 18 - 14
Stripping length mm 10
Tool
Screwdriver blade width mm 3.5
Push-in terminals
Terminal capacity main cable
Solid or stranded AWG 18 - 14
Main conducting paths
Rated impulse withstand voltage U
imp
V AC 8000
Overvoltage category/pollution degree III/3
Rated insulation voltage U
i
V AC 690
Rated operational voltage U
e
V AC 690
Safe isolation to EN 61140
between coil and contacts V AC 400
between the contacts V AC 400
Making capacity (p.f. to IEC/EN 60947)
Up to 690 V A 112
Breaking capacity
220 V 230 V A 70
380 V 400 V A 70
500 V A 50
660 V 690 V A 40
Short-circuit rating
Short-circuit protection maximum fuse
Type “2” coordination
400 V gG/gL 500 V A 20
690 V gG/gL 690 V A 16
Type “1” coordination
400 V gG/gL 500 V A 35
690 V gG/gL 690 V A 20
AC
AC-1
Rated operational current
Conventional free air thermal current, 3 pole, 50 - 60 Hz
Open
at 40 °C I
th
=I
e
A 22
at 50 °C I
th
=I
e
A 21
at 55 °C I
th
=I
e
A 21
at 60 °C I
th
=I
e
A 20
enclosed I
th
A 18
Conventional free air thermal current, 1 pole
open I
th
A 50
enclosed I
th
A 45
AC-3
Rated operational current
Open, 3-pole: 50 –60 Hz
Notes At maximum permissible ambient temperature (open.)
Also tested according to AC-3e.
220 V 230 V I
e
A 7
240 V I
e
A 7
380 V 400 V I
e
A 7
415 V I
e
A 7
440V I
e
A 7
06/18/2021 Eaton 277404 ED2021 V80.0 EN 3 / 13