Data Sheet

Opening delay ms 8 - 14
Arcing time ms 10
Electromagnetic compatibility (EMC)
Emitted interference to EN 60947-1
Interference immunity to EN 60947-1
Rating data for approved types
Switching capacity
Maximum motor rating
Three-phase
200 V
208 V
HP 10
230 V
240 V
HP 10
460 V
480 V
HP 20
575 V
600 V
HP 25
Single-phase
115 V
120 V
HP 2
230 V
240 V
HP 5
General use A 40
Auxiliary contacts
Pilot Duty
AC operated A600
DC operated P300
General Use
AC V 600
AC A 10
DC V 250
DC A 1
Short Circuit Current Rating SCCR
Basic Rating
SCCR kA 5
max. Fuse A 125
max. CB A 125
480 V High Fault
SCCR (fuse) kA 10/100
max. Fuse A 125/70 Class J
SCCR (CB) kA 10/65
max. CB A 50/32
600 V High Fault
SCCR (fuse) kA 10/100
max. Fuse A 125/125 Class J
SCCR (CB) kA 10/22
max. CB A 50/32
Special Purpose Ratings
Electrical Discharge Lamps (Ballast)
480V 60Hz 3phase, 277V 60Hz 1phase A 40
600V 60Hz 3phase, 347V 60Hz 1phase A 40
Incandescent Lamps (Tungsten)
480V 60Hz 3phase, 277V 60Hz 1phase A 40
600V 60Hz 3phase, 347V 60Hz 1phase A 40
Resistance Air Heating
480V 60Hz 3phase, 277V 60Hz 1phase A 40
600V 60Hz 3phase, 347V 60Hz 1phase A 40
Refrigeration Control (CSA only)
06/18/2021 Eaton 277247 ED2021 V80.0 EN 5 / 13