Data Sheet

440V I
e
A 32
500 V I
e
A 32
660 V 690 V I
e
A 18
Motor rating P kWh
220 V 230 V P kW 10
240V P kW 11
380 V 400 V P kW 15
415 V P kW 19
440 V P kW 20
500 V P kW 23
660 V 690 V P kW 17
AC-4
Open, 3-pole: 50 –60 Hz
220 V 230 V I
e
A 15
240 V I
e
A 15
380 V 400 V I
e
A 15
415 V I
e
A 15
440 V I
e
A 15
500 V I
e
A 15
660 V 690 V I
e
A 12
Motor rating P kWh
220 V 230 V P kW 4
240 V P kW 4.5
380 V 400 V P kW 7
415 V P kW 7.5
440 V P kW 8
500 V P kW 9
660 V 690 V P kW 10
DC
Rated operational current, open
DC-1
60 V I
e
A 40
110 V I
e
A 40
220 V I
e
A 40
Current heat loss
3 pole, at I
th
(60°) W 10.3
Current heat loss at I
e
to AC-3/400 V W 6.6
Impedance per pole mΩ 2.7
Magnet systems
Voltage tolerance
AC operated Pick-up x U
c
0.8 - 1.1
Drop-out voltage AC operated Drop-out x U
c
0.3 - 0.6
Power consumption of the coil in a cold state and 1.0 x U
S
50 Hz Pick-up VA 52
50 Hz Sealing VA 7.1
50 Hz Sealing W 2.1
60 Hz Pick-up VA 67
60 Hz Sealing VA 8.7
60 Hz Sealing W 2.1
Duty factor % DF 100
Changeover time at 100 % U
S
(recommended value)
Main contacts
AC operated
Closing delay ms 16 - 22
06/18/2021 Eaton 277247 ED2021 V80.0 EN 4 / 13