Data Sheet
380 V 400 V I
e
A 25
415 V I
e
A 25
440V I
e
A 25
500 V I
e
A 25
660 V 690 V I
e
A 15
Motor rating P kWh
220 V 230 V P kW 7.5
240V P kW 8.5
380 V 400 V P kW 11
415 V P kW 14.5
440 V P kW 15.5
500 V P kW 17.5
660 V 690 V P kW 14
AC-4
Open, 3-pole: 50 –60 Hz
220 V 230 V I
e
A 13
240 V I
e
A 13
380 V 400 V I
e
A 13
415 V I
e
A 13
440 V I
e
A 13
500 V I
e
A 13
660 V 690 V I
e
A 10
Motor rating P kWh
220 V 230 V P kW 3.5
240 V P kW 4
380 V 400 V P kW 6
415 V P kW 6.5
440 V P kW 7
500 V P kW 8
660 V 690 V P kW 8.5
DC
Rated operational current, open
DC-1
60 V I
e
A 40
110 V I
e
A 40
220 V I
e
A 40
Current heat loss
3 pole, at I
th
(60°) W 10.8
Current heat loss at I
e
to AC-3/400 V W 4.2
Impedance per pole mΩ 2.7
Magnet systems
Voltage tolerance
DC operated Pick-up x U
c
0.7 - 1.2
Notes RDC 24 (U
min
24 V DC/U
max
27 V DC)
Example: U
S
= 0.7 x U
min
- 1.2 x U
max
/ U
S
= 0.7 x 24V - 1.2 x 27V DC
DC operated Drop-out x U
c
0.15 - 0.6
Notes at least smoothed two-phase bridge rectifier or three-phase rectifier
Power consumption of the coil in a cold state and 1.0 x U
S
DC operated Pick-up W 12
DC operated Sealing W 0.9
Duty factor % DF 100
Changeover time at 100 % U
S
(recommended value)
Main contacts
DC operated ms
Closing delay ms
06/18/2021 Eaton 277178 ED2021 V80.0 EN 4 / 13










