Data Sheet
Motor rating P kWh
220 V 230 V P kW 3.5
240V P kW 4
380 V 400 V P kW 5.5
415 V P kW 7
440 V P kW 7.5
500 V P kW 7
660 V 690 V P kW 6.5
AC-4
Open, 3-pole: 50 –60 Hz
220 V 230 V I
e
A 7
240 V I
e
A 7
380 V 400 V I
e
A 7
415 V I
e
A 7
440 V I
e
A 7
500 V I
e
A 6
660 V 690 V I
e
A 5
Motor rating P kWh
220 V 230 V P kW 2
240 V P kW 2.2
380 V 400 V P kW 3
415 V P kW 3.4
440 V P kW 3.6
500 V P kW 3.5
660 V 690 V P kW 4.4
DC
Rated operational current, open
DC-1
60 V I
e
A 20
110 V I
e
A 20
220 V I
e
A 15
Current heat loss
3 pole, at I
th
(60°) W 2.5
Current heat loss at I
e
to AC-3/400 V W 0.9
Impedance per pole mΩ 2.5
Magnet systems
Voltage tolerance
AC operated Pick-up x U
c
0.8 - 1.1
Drop-out voltage AC operated Drop-out x U
c
0.3 - 0.6
Power consumption of the coil in a cold state and 1.0 x U
S
50/60 Hz Pick-up VA 27
25
50/60 Hz Sealing VA 4.2
3.3
50/60 Hz Sealing W 1.4
1.2
Duty factor % DF 100
Changeover time at 100 % U
S
(recommended value)
Main contacts
AC operated
Closing delay ms 15 - 21
Opening delay ms 9 - 18
Arcing time ms 10
Lifespan, mechanical; Coil 50/60 Hz
x 10
6
Mechanical lifespan at 50 Hz approx. 30% lower than under →Technical data
general
Electromagnetic compatibility (EMC)
Emitted interference to EN 60947-1
06/18/2021 Eaton 276873 ED2021 V80.0 EN 4 / 13