Data Sheet
Compatibilidad electromagnética (CEM)
Emisión de interferencias according to EN 60947-1
Inmunidad a interferencias according to EN 60947-1
Rating data for approved types
Poder de corte
Maximum motor rating
3 fases
200 V
208 V
HP 1.5
230 V
240 V
HP 2
460 V
480 V
HP 3
575 V
600 V
HP 5
1 fase
115 V
120 V
HP 0.25
230 V
240 V
HP 1
General use A 20
Contacto auxiliar
Pilot Duty
AC operated A600
DC operated P300
General Use
AC V 600
AC A 10
DC V 250
DC A 1
Short Circuit Current Rating SCCR
Basic Rating
SCCR kA 5
max. Fuse A 45
max. CB A 60
480 V High Fault
SCCR (fuse) kA 30/100
max. Fuse A 25 Class RK5/20 Class J
SCCR (CB) kA 65
max. CB A 16
600 V High Fault
SCCR (fuse) kA 30/100
max. Fuse A 25 Class RK5/20 Class J
Special Purpose Ratings
Electrical Discharge Lamps (Ballast)
480V 60Hz 3phase, 277V 60Hz 1phase A 12
600V 60Hz 3phase, 347V 60Hz 1phase A 12
Incandescent Lamps (Tungsten)
480V 60Hz 3phase, 277V 60Hz 1phase A 14
600V 60Hz 3phase, 347V 60Hz 1phase A 14
Resistance Air Heating
480V 60Hz 3phase, 277V 60Hz 1phase A 12
600V 60Hz 3phase, 347V 60Hz 1phase A 12
Refrigeration Control (CSA only)
LRA 480V 60Hz 3phase A 60
FLA 480V 60Hz 3phase A 10
LRA 600V 60Hz 3phase A 60
FLA 600V 60Hz 3phase A 10
16/06/2021 Eaton 276565 5 / 14