Data Sheet

between coil and auxiliary contacts V AC 400
between the auxiliary contacts V AC 400
Rated operational current A
Conventional free air thermal current, 1 pole
at 60 °C I
th
A 16
AC-15
220 V 230 V 240 V I
e
A 4
380 V 400 V 415 V I
e
A 4
500 V I
e
A 1.5
DC current
Switch-on and switch-off conditions based on DC-13, time constant as specified.
DC L/R ≦ 15 ms
Contacts in series: A
1 24 V A 10
1 60 V A 6
2 60 V A 10
1 110 V A 3
3 110 V A 6
1 220 V A 1
3 220 V A 5
DC L/R ≦ 50 ms
Contacts in series: A
3 24 V A 2.5
3 60 V A 1
3 110 V A 0.5
3 220 V A 0.25
DC-13 (6xP)
24 V I
e
A 2.5
60 V I
e
A 1
110 V I
e
A 0.5
220 V I
e
A 0.25
Control circuit reliability Failure rate λ
<10
-8
, < one failure at 100 million operations
(at U
e
= 24 V DC, U
min
= 17 V, I
min
= 5.4 mA)
Short-circuit rating without welding
Short-circuit protection maximum fuse
500 V A gG/gL 10
Current heat loss at I
th
AC operated W 2.6
DC operated W 2.6
Current heat loss per auxiliary circuit at I
e
(AC-15/230 V) CO 0.16
Rating data for approved types
Auxiliary contacts
Pilot Duty
AC operated A600
DC operated P300
General Use
AC V 600
AC A 10
DC V 250
DC A 1
Design verification as per IEC/EN 61439
Technical data for design verification
Rated operational current for specified heat dissipation I
n
A 4
Heat dissipation per pole, current-dependent P
vid
W 0.16
06/18/2021 Eaton 276421 ED2021 V80.0 EN 3 / 6