Data Sheet
3 220 V A 5
DC L/R ≦ 50 ms
Contacts in series: A
3 24 V A 4
3 60 V A 4
3 110 V A 2
3 220 V A 1
Control circuit reliability Failure rate λ
<10
-8
, < one failure at 100 million operations
(at U
e
= 24 V DC, U
min
= 17 V, I
min
= 5.4 mA)
Short-circuit rating without welding
Maximum overcurrent protective device
220 V 230 V 240 V PKZM0 4
380 V 400 V 415 V PKZM0 4
Short-circuit protection maximum fuse
500 V A gG/gL 10
Current heat loss at I
th
DC operated W 0.85
Magnet systems
Voltage tolerance
DC operated
Notes Smoothed DC, three-phase bridge rectifiers or smoothed double-wave rectification
Pick-up voltage 0.8 - 1.1
at 24 V: without auxiliary contact component (40 °C) Pick-up x U
c
0.7 - 1.3
Power consumption
DC operation
DC operated Pull-in =
sealing
W 3
duty factor % DF 100
Changeover time at 100 % U
S
(recommended value)
DC operated closing delay ms
Switching times, DC operated, max. closing delay ms 31
DC operated N/O contact opening delay ms
Switching times, DC actuated make contact Opening delay, max. ms 12
Rating data for approved types
Auxiliary contacts
Pilot Duty
AC operated A600
DC operated P300
General Use
AC V 600
AC A 15
DC V 250
DC A 1
Design verification as per IEC/EN 61439
Technical data for design verification
Rated operational current for specified heat dissipation I
n
A 15.5
Heat dissipation per pole, current-dependent P
vid
W 1
Equipment heat dissipation, current-dependent P
vid
W 0
Static heat dissipation, non-current-dependent P
vs
W 3
Heat dissipation capacity P
diss
W 0
Operating ambient temperature min. °C -25
Operating ambient temperature max. °C 60
IEC/EN 61439 design verification
10.2 Strength of materials and parts
10.2.2 Corrosion resistance Meets the product standard's requirements.
06/16/2021 Eaton 276414 ED2021 V80.0 EN 3 / 8