Mechanical shock resistance (IEC/EN 60068-2-27)
Half-sinusoidal shock, 10 ms
Basic unit with auxiliary contact module g
N/O contact g 7
N/C contact g 5
Degree of Protection IP20
Protection against direct contact when actuated from front (EN 50274) Finger and back-of-hand proof
Altitude m Max. 2000
Weight
AC operated kg 0.24
Terminal capacities
mm
2
Screw terminals
Solid
mm
2
1 x (0,75 - 4)
2 x (0,75 - 2,5)
Flexible with ferrule
mm
2
1 x (0.75 - 2.5)
2 x (0.75 - 2.5)
Solid or stranded AWG 18 - 14
Stripping length mm 10
Terminal screw M3.5
Pozidriv screwdriver Size 2
Standard screwdriver mm 0.8 x 5.5
1 x 6
Max. tightening torque Nm 1.2
Contacts
Positive operating contacts to ZH 1/457, including auxiliary contact module Yes
Rated impulse withstand voltage U
imp
V AC 6000
Overvoltage category/pollution degree III/3
Rated insulation voltage U
i
V AC 690
Rated operational voltage U
e
V AC 690
Safe isolation to EN 61140
between coil and auxiliary contacts V AC 400
between the auxiliary contacts V AC 400
Rated operational current A
Conventional free air thermal current, 1 pole
Open
at 60 °C I
th
=I
e
A 16
AC-15
220 V 230 V 240 V I
e
A 4
380 V 400 V 415 V I
e
A 4
500 V I
e
A 1.5
DC current
Notes Switch-on and switch-off conditions based on DC-13, time constant as specified.
DC L/R ≦ 15 ms
Contacts in series: A
1 24 V A 10
1 60 V A 6
2 60 V A 10
1 110 V A 3
3 110 V A 6
1 220 V A 1
3 220 V A 5
DC L/R ≦ 50 ms
Contacts in series: A
3 24 V A 4
3 60 V A 4
3 110 V A 2
06/18/2021 Eaton 276372 ED2021 V80.0 EN 2 / 8