Data Sheet
DATASHEET - XIOC-SER
Communication module for XC100/200, 24 V DC, serial, modbus, SUCOM-
A, suconet K
Part no. XIOC-SER
Catalog No. 267191
EL-Nummer
(Norway)
4519690
Delivery program
Function Communication modules
Compact I/O system for connection to XC100/200 Modular PLCs
XC100/200 expandable with up to 15 XI/OC modules
Optionally, screw terminals or spring-loaded terminals for digital/analog modules
Description Serial interface
RS232C, RS485, RS422
Modes of operation:
Transparent mode
MODBUS Master/Slave
SUCOM-A
Suconet-K slave
Technical data
General
Standards IEC/EN 61131-2
EN 50178
Ambient temperature °C 0 - +55
Storage ϑ °C -20 - +70
Vibration resistance 10 - 57 Hz ±0.075 mm
57 - 150 Hz ±1.0 mm
Mechanical shock resistance g 15
Shock duration 11 ms
Impact resistance 500 g/⌀ 50 mm ±25 g
Overvoltage category/pollution degree II/2
Protection class 1
Degree of Protection IP20
Emitted interference DIN/EN 55011/22, Class A
Weight kg 0.2
Power supply
Rated voltage U
e
V DC 24 (12)
Admissible range 20.4 – 28.8 (11.8 – 14.4)
Residual ripple % ≦ 5
Neutral poles
Duration of dip ms 10
Repetition rate s 1
Maximum power loss P
v
W 6.6
Interfaces
Built-in interfaces RS232(C), RS422, RS485
Protocol Tranparent-Modus, MODBUS Master/Slave, SUCOM-A, Suconet-K-Slave
Character formats 8E1, 8O1, 8N1, 8N2, 7E2, 7O2, 7N2, 7E1
Control and signal cables RTS, CTS, DTR, DSR, DCD
Data transfer rate kBit/s 0.3 …57.6
187.5, 375 (Suconet)
Potential isolation Yes (RS485, RS422)
Transmit/receive data 250 Byte per slave
120 Byte per slave (Suconet-K slave)
Bus terminating resistors Switchable for RS485, RS422
Plug arrangement RS232: 9 pole SUB-D plug
RS485, 422: plug terminal block
06/16/2021 Eaton 267191 ED2021 V80.0 EN 1 / 5