Data Sheet

Technical data
General
Standards IEC/EN 60947
Climatic proofing Damp heat, constant, to IEC 60068-2-78; damp heat, cyclical, to IEC 60068-2-30
Ambient temperature °C -25 - +70
Mounting position As required
Degree of Protection IP66, IP67
Terminal capacities
mm
2
Solid
mm
2
1 x (0.5 - 2.5)
Flexible with ferrule
mm
2
1 x (0.5 - 1.5)
Repetition accuracy mm 0.15
Contacts/switching capacity
Rated impulse withstand voltage U
imp
V AC 4000
Rated insulation voltage U
i
V 400
Overvoltage category/pollution degree III/3
Rated operational current I
e
A
AC-15
24 V I
e
A 6
220 V 230 V 240 V I
e
A 6
380 V 400 V 415 V I
e
A 4
DC-13
24 V I
e
A 3
110 V I
e
A 0.6
220 V I
e
A 0.3
Control circuit reliability
at 24 V DC/5 mA H
F
Fault
probability
< 10
-7
, < 1 fault in 10
7
operations
at 5 V DC/1 mA H
F
Fault
probability
< 5 x 10
-6
, < 1 failure at 5 x 10
6
operations
Supply frequency Hz max. 400
Short-circuit rating to IEC/EN 60947-5-1
max. fuse A gG/gL 6
Rated conditional short-circuit current kA 1
Mechanical variables
Lifespan, mechanical Operations
x 10
6
8
Mechanical shock resistance (half-sinusoidal shock, 20 ms)
Standard-action contact g 25
Operating frequency Operations/h ≦ 6000
Actuation
Mechanical
Actuating force at beginning/end of stroke N 1.0/8.0
Actuating torque of rotary drives Nm 0.2
Max. operating speed with DIN cam m/s 1.5
Notes for angle of actuation α = 30°, L = 125 mm
Design verification as per IEC/EN 61439
Technical data for design verification
Rated operational current for specified heat dissipation I
n
A 6
Heat dissipation per pole, current-dependent P
vid
W 0.17
Equipment heat dissipation, current-dependent P
vid
W 0
Static heat dissipation, non-current-dependent P
vs
W 0
Heat dissipation capacity P
diss
W 0
Operating ambient temperature min. °C -25
Operating ambient temperature max. °C 70
IEC/EN 61439 design verification
06/16/2021 Eaton 266154 ED2021 V80.0 EN 2 / 5