Datasheet
415 V 50/60 Hz Operations 5000
690 V 50/60 Hz Operations 3000
AC--3
400 V 50/60 Hz Operations 2000
415 V 50/60 Hz Operations 2000
690 V 50/60 Hz Operations 2000
Max. operating frequency Ops/h 60
Total break time at short-circuit ms < 10
Terminal capacity
Standard equipment Screw connection
Optional accessories Box terminal
Tunnel terminal
connection on rear
Round copper conductor
Box terminal
Solid
mm
2
2 x 16
Stranded
mm
2
1 x (35 - 240)
2 x (25-120)
Tunnel terminal
Solid
mm
2
1 x 16
Stranded
1-hole
mm
2
1 x (16 - 185)
Double hole fitting
mm
2
2 x (50 - 240)
Bolt terminal and rear-side connection
Direct on the switch
Solid
mm
2
1 x 16
2 x 16
Stranded
mm
2
1 x (25 - 240)
2 x (25 - 240)
Connection width extension
mm
2
Connection width extension
mm
2
2 x 300
Al circular conductor
Tunnel terminal
Solid
mm
2
1 x 16
Stranded
Stranded
mm
2
1 x (25 - 185)
2)
Double hole
mm
2
1 x (50 - 240)
2 x (50 - 240)
2)
Up to 240 mm² can be connected depending on the cable manufacturer.
Bolt terminal and rear-side connection
Direct on the switch
Solid
mm
2
1 x 16
2 x (10 - 16)
Stranded
mm
2
1 x (25 - 120)
2 x (25 - 120)
Cu strip (number of segments x width x segment thickness)
Box terminal
min. mm 6 x 16 x 0.8
max. mm 10 x 24 x 1.0
+ 5 x 24 x 1.0
(2 x) 8 x 24 x 1.0
Bolt terminal and rear-side connection
Flat copper strip, with holes min. mm 6 x 16 x 0.8
Flat copper strip, with holes max. mm 10 x 32 x 1.0 + 5 x 32 x 1.0
Connection width extension mm (2 x) 10 x 50 x 1.0
Copper busbar (width x thickness) mm
Bolt terminal and rear-side connection
Screw connection M10
06/18/2021 Eaton 265894 ED2021 V80.0 EN 3 / 10