Data Sheet
DATASHEET - DILM115-22(RAC240)
Contactor, 380 V 400 V 55 kW, 2 N/O, 2 NC, RAC 240: 190 - 240 V 50/60 Hz,
AC operation, Screw terminals
Part no. DILM115-22(RAC240)
Catalog No. 239578
Alternate Catalog
No.
XTCE115G22B
EL-Nummer
(Norway)
4110247
Delivery program
Product range Contactors
Application Contactors for Motors
Subrange Complete devices up to 170 A
Utilization category AC-1: Non-inductive or slightly inductive loads, resistance furnaces
AC-3/AC-3e: Normal AC induction motors: Starting, switching off while running
AC-4: Normal AC induction motors: starting, plugging, reversing, inching
Connection technique Screw terminals
Notes Also suitable for motors with efficiency class IE3.
Also tested according to AC-3e.
Rated operational current
AC-3
380 V 400 V I
e
A 115
AC-1
Conventional free air thermal current, 3 pole, 50 - 60 Hz
Open
at 40 °C I
th
=I
e
A 160
enclosed I
th
A 115
Conventional free air thermal current, 1 pole
open I
th
A 325
enclosed I
th
A 285
Max. rating for three-phase motors, 50 - 60 Hz
AC-3
220 V 230 V P kW 37
380 V 400 V P kW 55
660 V 690 V P kW 90
AC-4
220 V 230 V P kW 17
380 V 400 V P kW 28
660 V 690 V P kW 43
Contacts
N/O = Normally open 2 N/O
N/C = Normally closed 2 NC
Instructions Contacts to EN 50 012.
integrated suppressor circuit in actuating electronics
with mirror contact.
Contact sequence
Actuating voltage RAC 240: 190 - 240 V 50/60 Hz
Voltage AC/DC AC operation
Technical data
General
Standards IEC/EN 60947, VDE 0660, UL, CSA
06/18/2021 Eaton 239578 ED2021 V80.0 EN 1 / 13