Data Sheet

Longevidad, mecánica; bobina 50/60 Hz
x 10
6
Mechanical lifespan at 50 Hz approx. 30% lower than under “General”
Compatibilidad electromagnética (CEM)
Emisión de interferencias según EN 60947-1
Inmunidad a interferencias según EN 60947-1
Rating data for approved types
Poder de corte
Maximum motor rating
3 fases
200 V
208 V
HP 30
230 V
240 V
HP 40
460 V
480 V
HP 75
575 V
600 V
HP 100
1 fase
115 V
120 V
HP 7.5
230 V
240 V
HP 15
General use A 125
Short Circuit Current Rating SCCR
Basic Rating
SCCR kA 10
max. Fuse A 600
max. CB A 600
480 V High Fault
SCCR (fuse) kA 30/100
max. Fuse A 300/300 Class J
SCCR (CB) kA 65
max. CB A 250
600 V High Fault
SCCR (fuse) kA 30/100
max. Fuse A 300/300 Class J
SCCR (CB) kA 30
max. CB A 350
Special Purpose Ratings
Electrical Discharge Lamps (Ballast)
480V 60Hz 3phase, 277V 60Hz 1phase A 100
600V 60Hz 3phase, 347V 60Hz 1phase A 100
Incandescent Lamps (Tungsten)
480V 60Hz 3phase, 277V 60Hz 1phase A 100
600V 60Hz 3phase, 347V 60Hz 1phase A 100
Resistance Air Heating
480V 60Hz 3phase, 277V 60Hz 1phase A 100
600V 60Hz 3phase, 347V 60Hz 1phase A 100
Refrigeration Control (CSA only)
LRA 480V 60Hz 3phase A 540
FLA 480V 60Hz 3phase A 90
LRA 600V 60Hz 3phase A 420
FLA 600V 60Hz 3phase A 70
Definite Purpose Ratings (100,000 cycles acc. to UL 1995)
LRA 480V 60Hz 3phase A 570
FLA 480V 60Hz 3phase A 95
Elevator Control
200V 60Hz 3phase HP 20
200V 60Hz 3phase A 62.1
16/06/2021 Eaton 239488 5 / 13