Data Sheet
DATASHEET - PFDM-125/4/003-A
Residual current circuit-breaker, 125A, 4p, 03mA, A-Char
Part no. PFDM-125/4/003-A
Catalog No. 235920
Design verification as per IEC/EN 61439
Technical data for design verification
Rated operational current for specified heat dissipation I
n
A 125
Heat dissipation per pole, current-dependent P
vid
W 0
Equipment heat dissipation, current-dependent P
vid
W 33.6
Static heat dissipation, non-current-dependent P
vs
W 0
Heat dissipation capacity P
diss
W 0
Operating ambient temperature min. °C -25
Operating ambient temperature max. °C 60
Starting at 40 °C, the max. permissible continuous current decreases by 2.2% for
every 1 °C
Technical data ETIM 7.0
Circuit breakers and fuses (EG000020) / Residual current circuit breaker (RCCB) (EC000003)
Electric engineering, automation, process control engineering / Electrical installation, device / Residual current protection system / Residual current circuit breaker (RCCB)
(ecl@ss10.0.1-27-14-22-01 [AAB906014])
Number of poles 4
Rated voltage V 400
Rated current A 125
Rated fault current mA 30
Rated insulation voltage Ui V 400
Rated impulse withstand voltage Uimp kV 4
Mounting method DIN rail
Leakage current type A
Selective protection No
Short-time delayed tripping No
Short-circuit breaking capacity (Icw) kA 10
Surge current capacity kA 0.2
Frequency 50 Hz
Additional equipment possible Yes
With interlocking device Yes
Degree of protection (IP) IP20
Width in number of modular spacings 4
Built-in depth mm 71.5
Ambient temperature during operating °C -25 - 60
Pollution degree 2
Connectable conductor cross section multi-wired mm² 1.5 - 16
Connectable conductor cross section solid-core mm² 1.5 - 50
06/18/2021 Eaton 235920 ED2021 V80.0 EN 1 / 2