Data Sheet
Mounting position
Direction of incoming supply as required
Degree of protection
Device IP20
Terminations IP00
Protection against direct contact when actuated from front (EN 50274) Finger and back-of-hand proof
Mechanical shock resistance half-sinusoidal shock 10 ms to IEC 60068-2-27 g 25
Altitude m Max. 2000
Terminal capacity main cable
Spring-loaded terminals
Solid
mm
2
1 x (0.75…2.5)
2 x (0.75…2.5)
Flexible with ferrule to DIN 46228
mm
2
1 x (0.75…2.5)
2 x (0.75…2.5)
Solid or stranded AWG 18…14
Stripping length mm 10
Specified tightening torque for terminal screws
Control circuit cables Nm 1
Main conducting paths
Rated impulse withstand voltage U
imp
V AC 6000
Overvoltage category/pollution degree III/3
Rated operational voltage U
e
V AC 690
Rated uninterrupted current = rated operational current I
u
= I
e
A 10
Rated frequency f Hz 40 - 60
Current heat loss (3 pole at operating temperature) W 6.48
Impedance per pole mΩ 21
Lifespan, mechanical Operations
x 10
6
0.1
Lifespan, electrical (AC-3 at 400 V)
Lifespan, electrical Operations
x 10
6
0.1
Max. operating frequency Ops/h 40
Short-circuit rating
DC
Short-circuit rating kA 60
Notes up to 250 V
Motor switching capacity
AC-3 (up to 690V) A 10
DC-5 (up to 250V) A 10 (3 contacts in series)
Trip blocks
Temperature compensation
to IEC/EN 60947, VDE 0660 °C - 5 … 40
Operating range °C - 25 … 55
Temperature compensation residual error for T > 40 °C ≦ 0.25 %/K
Setting range of overload releases x I
u
0.6 - 1
short-circuit release Basic device, fixed: 15.5 x I
u
Short-circuit release tolerance ± 20%
Phase-failure sensitivity IEC/EN 60947-4-1, VDE 0660 Part 102
Rating data for approved types
Switching capacity
Maximum motor rating
Three-phase
200 V
208 V
HP 3
230 V
240 V
HP 3
06/18/2021 Eaton 229678 ED2021 V80.0 EN 2 / 10