Technical Data 10164
Effective September 2015
Bussmann series
500 Volts gG/gL NH Fuse links
EATON www.eaton.com
Time-current curves - NH Size 03
Technical data - NH size 03
Part numbers
with metal
gripping lugs
Part numbers
with insulated
metal gripping
lugs
Fuse link
size
Rated
current
(Amp)
Rated
voltage
(V a.c.)
I
2
t (Amps
2
Seconds)
Watts loss
Net weight
per fuse
(kg)
Minimum
pre-arcing
*I
1
120kA
at 500 V a.c.
250NHG03B 250NHG03BI 03 250 500 160,800 642,900 20 0.64
315NHG03B 315NHG03BI 315 361,700 1,446,500 21
355NHG03B 355NHG03BI 355 446,500 1,785,800 27
400NHG03B 400NHG03BI 400 642,900 2,571,500 30
*I
1
is the maximum breaking capacity test at rated voltage according to IEC 60269 requirements