Data Sheet
380 V 400 V I
e
A 500
415 V I
e
A 500
440V I
e
A 500
500 V I
e
A 500
660 V 690 V I
e
A 325
1000 V I
e
A 95
Motor rating P kWh
220 V 230 V P kW 155
240V P kW 170
380 V 400 V P kW 265
415 V P kW 290
440 V P kW 315
500 V P kW 355
660 V 690 V P kW 300
1000 V P kW 132
AC-4
Rated operational current
Open, 3-pole: 50 –60 Hz
220 V 230 V I
e
A 360
240 V I
e
A 360
380 V 400 V I
e
A 360
415 V I
e
A 360
440 V I
e
A 360
500 V I
e
A 360
660 V 690 V I
e
A 260
1000 V I
e
A 95
Motor rating P kWh
220 V 230 V P kW 112
240 V P kW 122
380 V 400 V P kW 200
415 V P kW 216
440 V P kW 229
500 V P kW 250
660 V 690 V P kW 240
1000 V P kW 132
Condensor operation
Individual compensation, rated operational current I
e
of three-phase capacitors
Open
up to 525 V A 307
690 V A 177
Max. inrush current peak x I
e
30
Component lifespan Operations
x 10
6
0.1
Max. operating frequency Ops/h 200
DC
Rated operational current, open
DC-1
Notes see DILDC300/DILDC600 or on request
Current heat loss
3 pole, at I
th
(60°) W 113
Current heat loss at I
e
to AC-3/400 V W 58
Impedance per pole mΩ 0.089
Magnet systems
Voltage tolerance
U
S
110 - 250 V 40-60 Hz
110 - 350 V DC
06/18/2021 Eaton 208213 ED2021 V80.0 EN 4 / 12