Data Sheet

AC A 15
DC V 250
DC A 1
Short Circuit Current Rating SCCR
Basic Rating
SCCR kA 30
max. Fuse A 800
max. CB A 600
480 V High Fault
SCCR (fuse) kA 30/100
max. Fuse A 800/600 Class J
SCCR (CB) kA 100
max. CB A 600
600 V High Fault
SCCR (fuse) kA 30/100
max. Fuse A 800/600 Class J
SCCR (CB) kA 30
max. CB A 600
Special Purpose Ratings
Definite Purpose Ratings (100,000 cycles acc. to UL 1995)
LRA 480V 60Hz 3phase A 3300
FLA 480V 60Hz 3phase A 550
LRA 600V 60Hz 3phase A 3120
FLA 600V 60Hz 3phase A 420
Design verification as per IEC/EN 61439
Technical data for design verification
Rated operational current for specified heat dissipation I
n
A 400
Heat dissipation per pole, current-dependent P
vid
W 12.33
Equipment heat dissipation, current-dependent P
vid
W 0
Static heat dissipation, non-current-dependent P
vs
W 7.9
Heat dissipation capacity P
diss
W 0
Operating ambient temperature min. °C -40
Operating ambient temperature max. °C 60
IEC/EN 61439 design verification
10.2 Strength of materials and parts
10.2.2 Corrosion resistance Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat Meets the product standard's requirements.
10.2.3.3 Verification of resistance of insulating materials to abnormal heat
and fire due to internal electric effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation Meets the product standard's requirements.
10.2.5 Lifting Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances Meets the product standard's requirements.
10.5 Protection against electric shock Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections Is the panel builder's responsibility.
10.8 Connections for external conductors Is the panel builder's responsibility.
10.9 Insulation properties
10.9.2 Power-frequency electric strength Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material Is the panel builder's responsibility.
06/16/2021 Eaton 208209 ED2021 V80.0 EN 6 / 12