Data Sheet

380 V 400 V I
e
A 250
415 V I
e
A 250
440V I
e
A 250
500 V I
e
A 250
660 V 690 V I
e
A 185
1000 V I
e
A 76
Motor rating P kWh
220 V 230 V P kW 75
240V P kW 85
380 V 400 V P kW 132
415 V P kW 143
440 V P kW 152
500 V P kW 173
660 V 690 V P kW 170
1000 V P kW 108
AC-4
Rated operational current
Open, 3-pole: 50 –60 Hz
220 V 230 V I
e
A 200
240 V I
e
A 200
380 V 400 V I
e
A 200
415 V I
e
A 200
440 V I
e
A 200
500 V I
e
A 200
660 V 690 V I
e
A 150
1000 V I
e
A 76
Motor rating P kWh
220 V 230 V P kW 62
240 V P kW 68
380 V 400 V P kW 110
415 V P kW 117
440 V P kW 125
500 V P kW 138
660 V 690 V P kW 137
1000 V P kW 108
Condensor operation
Individual compensation, rated operational current I
e
of three-phase capacitors
Open
up to 525 V A 220
690 V A 133
Max. inrush current peak x I
e
30
Component lifespan Operations
x 10
6
0.1
Max. operating frequency Ops/h 200
DC
Rated operational current, open
DC-1
Notes see DILDC300/DILDC600 or on request
Current heat loss
3 pole, at I
th
(60°) W 55
Current heat loss at I
e
to AC-3/400 V W 28
Impedance per pole mΩ 0.15
Magnet systems
Voltage tolerance
U
S
110 - 250 V 40-60 Hz
110 - 350 V DC
06/18/2021 Eaton 208201 ED2021 V80.0 EN 4 / 12