Data Sheet

Tool
Main cable
Width across flats mm 16
Control circuit cables
Pozidriv screwdriver Size 2
Main conducting paths
Rated impulse withstand voltage U
imp
V AC 8000
Overvoltage category/pollution degree III/3
Rated insulation voltage U
i
V AC 1000
Rated operational voltage U
e
V AC 1000
Safe isolation to EN 61140
between coil and contacts V AC 1000
between the contacts V AC 1000
Making capacity (p.f. to IEC/EN 60947) A 3000
Breaking capacity
220 V 230 V A 2500
380 V 400 V A 2500
500 V A 2500
660 V 690 V A 2500
1000 V A 760
Component lifespan
AC1: See → Engineering, characteristic curves
AC3: See → Engineering, characteristic curves
AC4: See → Engineering, characteristic curves
Short-circuit rating
Short-circuit protection maximum fuse
Type “2” coordination
400 V gG/gL 500 V A 400
690 V gG/gL 690 V A 315
1000 V gG/gL 1000 V A 160
Type “1” coordination
400 V gG/gL 500 V A 400
690 V gG/gL 690 V A 400
1000 V gG/gL 1000 V A 200
AC
AC-1
Rated operational current
Conventional free air thermal current, 3 pole, 50 - 60 Hz
Open
at 40 °C I
th
=I
e
A 430
at 50 °C I
th
=I
e
A 380
at 55 °C I
th
=I
e
A 365
at 60 °C I
th
=I
e
A 350
enclosed I
th
A 300
Notes At maximum permissible ambient air temperature.
Conventional free air thermal current, 1 pole
Note at maximum permissible ambient air temperature
open I
th
A 825
enclosed I
th
A 742
AC-3
Rated operational current
Open, 3-pole: 50 –60 Hz
Notes At maximum permissible ambient temperature (open.)
220 V 230 V I
e
A 250
240 V I
e
A 250
06/18/2021 Eaton 208201 ED2021 V80.0 EN 3 / 12