Datasheet

Rated permanent current Iu A 100
Rated permanent current at AC-23, 400 V A 100
Rated permanent current at AC-21, 400 V A 100
Rated operation power at AC-3, 400 V kW 37
Rated short-time withstand current lcw kA 2
Rated operation power at AC-23, 400 V kW 55
Switching power at 400 V kW 55
Conditioned rated short-circuit current Iq kA 4
Number of poles 4
Number of auxiliary contacts as normally closed contact 0
Number of auxiliary contacts as normally open contact 0
Number of auxiliary contacts as change-over contact 0
Motor drive optional No
Motor drive integrated No
Voltage release optional No
Device construction Complete device in housing
Suitable for ground mounting Yes
Suitable for front mounting 4-hole No
Suitable for front mounting centre No
Suitable for distribution board installation No
Suitable for intermediate mounting No
Colour control element Red
Type of control element Door coupling rotary drive
Interlockable Yes
Type of electrical connection of main circuit Screw connection
Degree of protection (IP), front side IP65
Degree of protection (NEMA) 12
Approvals
Product Standards UL 60947-4-1;CSA - C22.2 No. 60947-4-1-14; CSA-C22.2 No. 94; IEC/EN 60947-3; CE
marking
UL File No. E36332
UL Category Control No. NLRV
CSA File No. 12528
CSA Class No. 3211-05
North America Certification UL listed, CSA certified
Specially designed for North America Yes, additional labeling according to UL on the enclosure in combination with "+NA-
I5" (105869)
Suitable for Branch circuits, suitable as motor disconnect
Degree of Protection IEC: IP65; UL/CSA Type 1, 12
Dimensions
06/16/2021 Eaton 207379 ED2021 V80.0 EN 5 / 6