Datasheet
AC-23A
Motor rating AC-23A, 50 - 60 Hz P kW
230 V P kW 7.5
400 V 415 V P kW 15
500 V P kW 18.5
690 V P kW 15
Rated operational current motor load switch
230 V I
e
A 32
400 V 415 V I
e
A 32
500 V I
e
A 30
690 V I
e
A 19.8
DC
DC-1, Load-break switches L/R = 1 ms
Rated operational current I
e
A 32
Voltage per contact pair in series V 60
DC-23A, motor load switch L/R = 15 ms
24 V
Rated operational current I
e
A 25
Contacts Quantity 1
48 V
Rated operational current I
e
A 25
Contacts Quantity 2
60 V
Rated operational current I
e
A 25
Contacts Quantity 2
120 V
Rated operational current I
e
A 12
Contacts Quantity 3
Control circuit reliability at 24 V DC, 10 mA Fault
probability
H
F
< 10
-5
,< 1 failure in 100,000 switching operations
Terminal capacities
Solid or stranded
mm
2
1 x (1,5 - 6)
2 x (1,5 - 6)
Flexible with ferrules to DIN 46228
mm
2
1 x (1 - 4)
2 x (1 - 4)
Terminal screw M4
Tightening torque for terminal screw Nm 1.6
Technical safety parameters:
Notes B10
d
values as per EN ISO 13849-1, table C1
Rating data for approved types
Terminal capacity
Terminal screw M4
Tightening torque lb-in 14.128
Design verification as per IEC/EN 61439
Technical data for design verification
Rated operational current for specified heat dissipation I
n
A 32
Heat dissipation per pole, current-dependent P
vid
W 1.8
Equipment heat dissipation, current-dependent P
vid
W 0
Static heat dissipation, non-current-dependent P
vs
W 0
Heat dissipation capacity P
diss
W 0
Operating ambient temperature min. °C -25
Operating ambient temperature max. °C 40
IEC/EN 61439 design verification
10.2 Strength of materials and parts
10.2.2 Corrosion resistance Meets the product standard's requirements.
06/18/2021 Eaton 207315 ED2021 V80.0 EN 3 / 5