Data Sheet
DATASHEET - EASY-E4-AC-8RE1P
I/O expansion, For use with easyE4, 100 - 240 V AC, 110 - 220 V DC (cULus:
100-110 V DC)), Inputs/Outputs expansion (number) digital: 4, Push-In
Part no. EASY-E4-AC-8RE1P
Catalog No. 197514
Delivery program
Product range Control relays easyE4
Subrange I/O expansions digital
Basic function easyE4 extensions
Description Input/output extension for easyE4 control relay
Expandable with the easyE4 series of digital input/output expansions with easy-E4-
CONNECT1 connector (Item Y7-197225)
Rated operating voltage 100 to 240V AC or 100 to 240V DC
For cULus, 100–110 VDC applies to all VDC specifications.
4 digital inputs with 100–240 VAC or 100–240 VDC
4 relay outputs for 12–250 VAC or 12–220 VDC
Push in terminals
Inputs
Inputs expansion (number) digital: 4
Additional features
Software EASYSOFT-SWLIC/easySoft 7
Supply voltage 100 - 240 V AC, 100 - 240 V DC (cULus: 100 - 110 V DC)
For use with easyE4
Technical data
General
Standards EN 61000-6-2
EN 61000-6-3
IEC 60068-2-6
IEC 60068-2-27
IEC 60068-2-30
IEC/EN 61131-2
EN 61010
EN 50178
Approvals
Approvals cULus
certificate CE
shipping classification DNV GL
Dimensions (W x H x D) mm 35.5 x 90 x 58
Weight kg 0.117
Mounting Top-hat rail IEC/EN 60715, 35 mm or screw fixing using fixing brackets ZB4-101-GF1
(accessories)
Connection type Push-in terminals
Terminal capacities
Push-in terminals
Solid
mm
2
0,2 - 0,4
flexible
mm
2
0.2 - 2.5
Solid or flexible conductor, with ferrule
mm
2
0,25 - 1,5
Solid or stranded AWG 24 - 14
Standard screwdriver mm 0.4 x 2.5
Stripping length mm 8
Climatic environmental conditions
Operating ambient temperature °C -25 to 55, cold as per IEC 60068-2-1, heat as per IEC 60068-2-2
Condensation Take appropriate measures to prevent condensation
06/18/2021 Eaton Y7-197514 ED2021 V80.0 EN 1 / 6