Data Sheet

Push-in terminals
mm
2
0.2 - 2.5
AWG 24 - 14
Main conducting paths
Rated operational voltage U
e
V AC 500
Operational voltage range V
Operating voltage range min. V 42
Operating voltage range max. V 550
Rated operational current
AC-51 I
e
A 3
AC-53a I
e
A 3
AC-53a: Please note possible derating.
Setting range of overload releases I
r
A_x 0,18 - 3
Release class CLASS 10
Heat dissipation P
V
W 0.1 - 2.5
Control section
Rated control voltage U
s
V DC 24
Control voltage range V 19,2 - 30 V DC
Residual ripple on the input voltage % ≦ 5
Rated control current I
s
mA 60
Current draw inrush mA 120
Actuating circuit (ON, L, R)
Rated actuation voltage U
c
V 24
Switching level "Low" V -3 - +9.6 V DC
Switching level "confirm Off" V < 5 V DC
Switching level "High" V 19.2 - 30 V DC
Rated actuating current I
c
mA 7
Electromagnetic compatibility (EMC)
Radio interference suppression EN 55011
EN 61000-6-3, Class A (emitted interference, radiated)
Design verification as per IEC/EN 61439
Technical data for design verification
Rated operational current for specified heat dissipation I
n
A 3
Heat dissipation per pole, current-dependent P
vid
W 0
Equipment heat dissipation, current-dependent P
vid
W 2.5
Static heat dissipation, non-current-dependent P
vs
W 2
Heat dissipation capacity P
diss
W 0
Operating ambient temperature min. °C -5
Operating ambient temperature max. °C 55
If necessary, Allow for derating
IEC/EN 61439 design verification
10.2 Strength of materials and parts
10.2.2 Corrosion resistance Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat Meets the product standard's requirements.
10.2.3.3 Verification of resistance of insulating materials to abnormal heat
and fire due to internal electric effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation Meets the product standard's requirements.
10.2.5 Lifting Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances Meets the product standard's requirements.
10.5 Protection against electric shock Does not apply, since the entire switchgear needs to be evaluated.
06/18/2021 Eaton 192384 ED2021 V80.0 EN 2 / 5