Datasheet

Technical data ETIM 7.0
Circuit breakers and fuses (EG000020) / Residual current circuit breaker (RCCB) (EC000003)
Electric engineering, automation, process control engineering / Electrical installation, device / Residual current protection system / Residual current circuit breaker (RCCB)
(ecl@ss10.0.1-27-14-22-01 [AAB906014])
Number of poles 4
Rated voltage V 230
Rated current A 40
Rated fault current mA 30
Rated insulation voltage Ui V 440
Rated impulse withstand voltage Uimp kV 4
Mounting method DIN rail
Leakage current type Other
Selective protection No
Short-time delayed tripping Yes
Short-circuit breaking capacity (Icw) kA 10
Surge current capacity kA 3
Frequency 50 Hz
Additional equipment possible Yes
With interlocking device Yes
Degree of protection (IP) IP20
Width in number of modular spacings 4
Built-in depth mm 70.5
Ambient temperature during operating °C -25 - 60
Pollution degree 2
Connectable conductor cross section multi-wired mm² 1.5 - 16
Connectable conductor cross section solid-core mm² 1.5 - 35
06/18/2021 Eaton Industries GmbH
http://www.eaton.eu
© 06/2021 by Eaton Industries GmbH
Eaton 187456 ED2021 V80.0 EN