Datasheet
Built-in width mm 35 (2TE)
Mounting Quick attachment with 2 latch positions for DIN-rail IEC/EN 60715
Degree of Protection IP20, IP40 with suitable enclosure
Terminals top and bottom Open mouthed/lift terminals
Terminal protection DGUV VS3, EN 50274
Terminal cross-section
Solid
mm
2
1.5 - 35
Stranded
mm
2
2 x 16
Terminal cross-section M5 (with cross-recessed screw as defined in EN ISO 4757-Z2, Pozidriv PZ2)
Tightening torque of fixing screws N/m 2 - 2.4
Thickness of busbar material mm 0.8 - 2
Admissible ambient temperature range °C -25 - +40
Permissible storage and transport temperatures °C -35 - +60
Climatic proofing 25-55°C/90-95% relative humidity according to IEC 60068-2
Mounting position As required
Contact position indicator red / green
Thickness of busbar material mm
Material thickness mm 0.8 - 2
Design verification as per IEC/EN 61439
Technical data for design verification
Rated operational current for specified heat dissipation I
n
A 40
Equipment heat dissipation, current-dependent P
vid
W 13.1
Operating ambient temperature min. °C -25
Operating ambient temperature max. °C 60
Starting at 40 °C, the max. permissible continuous current decreases by 2.5% for
every 1 °C
IEC/EN 61439 design verification
10.2 Strength of materials and parts
10.2.2 Corrosion resistance Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat Meets the product standard's requirements.
10.2.3.3 Verification of resistance of insulating materials to abnormal heat
and fire due to internal electric effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation Meets the product standard's requirements.
10.2.5 Lifting Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances Meets the product standard's requirements.
10.5 Protection against electric shock Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections Is the panel builder's responsibility.
10.8 Connections for external conductors Is the panel builder's responsibility.
10.9 Insulation properties
10.9.2 Power-frequency electric strength Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material Is the panel builder's responsibility.
10.10 Temperature rise The panel builder is responsible for the temperature rise calculation. Eaton will
provide heat dissipation data for the devices.
10.11 Short-circuit rating Is the panel builder's responsibility. The specifications for the switchgear must be
observed.
10.12 Electromagnetic compatibility Is the panel builder's responsibility. The specifications for the switchgear must be
observed.
10.13 Mechanical function The device meets the requirements, provided the information in the instruction
leaflet (IL) is observed.
06/18/2021 Eaton 187456 ED2021 V80.0 EN 2 / 3