Datasheet
DATASHEET - PFIM-40/4/003-G/F
Residual current circuit breaker (RCCB), 40A, 4p, 30mA, type G/F
Part no. PFIM-40/4/003-G/F
Catalog No. 187456
Similar to illustration
Delivery program
Basic function Residual current circuit-breakers
Number of poles 4 pole
Application Residual current circuit-breaker for residential and commercial applications
Rated current I
n
A 40
Rated short-circuit strength I
cn
kA 10 with back-up fuse
Rated fault current I
ΔN
A 0.03
Type Typ G/F (ÖVE E 8601)
Tripping s… Short time-delayed
Product range PFIM-F
Sensitivity pulse-current sensitive - frequency composition (10 Hz, 50 Hz, 1000 Hz)
Impulse withstand current Surge-proof, 3 kA
Technical data
Electrical
Types conform to IEC/EN 62423
Current test marks As per inscription
Standards IEC/EN 61008
Rated operational voltage U
e
V
U
e
V AC
Rated operating voltage U
e
V AC 230/400
Rated voltage according to IEC/EN 60947-2 U
n
V AC 230/400
Rated frequency f Hz 50
Limit values of the operating voltage
Test circuit V AC 196 - 264
Comment for range of the test button 3-phase application without N (400V AC Phase-Phase) not allowed
Sensitivity pulse-current sensitive - frequency composition (10 Hz, 50 Hz, 1000 Hz)
Rated insulation voltage U
i
V 440
Rated impulse withstand voltage U
imp
kV 4
Rated short-circuit strength I
cn
kA 10 with back-up fuse
Max. admissible back-up fuse
Short-circuit gG/gL A 63
Overload gG/gL A 25
Rated making and breaking capacity / Rated residual making and breaking
capacity
I
m
/ I
Δm
A 500
lifespan
Electrical Operations ≧ 4000
Mechanical Operations ≧ 20000
References
Auxiliary switch for subsequent installation Z-HK 248432
Tripping signal contact for subsequent installation Z-NHK 248434
Remote control and automatic switching device Z-FW/LP 248296
Compact enclosure KLV-TC-4 276241
Sealing cover set Z-RC/AK-4MU 101062
Mechanical
Standard front dimension mm 45
Device height mm 80
06/18/2021 Eaton 187456 ED2021 V80.0 EN 1 / 3