Data Sheet

Storage ϑ °C -40 - +60
Radio interference level
Radio interference class (EMC) C2, C3, depending on the motor cable length, the connected load, and ambient
conditions. External radio interference suppression filters (optional) may be
necessary.
Environment (EMC) 1st and 2nd environments as per EN 61800-3
maximum motor cable length I m C2 ≤ 5 m
C3 ≤ 25 m
Mounting position Vertical
Altitude m 0 - 1000 m above sea level
Above 1000 m: 1% derating for every 100 m
max. 4000 m
Degree of Protection IP20/NEMA0
Protection against direct contact BGV A3 (VBG4, finger- and back-of-hand proof)
Main circuit
Supply
Rated operational voltage U
e
400 V AC, 3-phase
480 V AC, 3-phase
Mains voltage (50/60Hz) U
LN
V 380 (-10%) - 480 (+10%)
Input current (150% overload) I
LN
A 11.5
System configuration AC supply systems with earthed center point
Supply frequency f
LN
Hz 50/60
Frequency range f
LN
Hz 48 - 62
Mains switch-on frequency Maximum of one time every 30 seconds
Power section
Function Variable frequency drive with internal DC link and IGBT inverter
Overload current (150% overload) I
L
A 14.25
max. starting current (High Overload) I
H
% 175
Note about max. starting current for 2,5 seconds every 600 seconds
Output voltage with V
e
U
2
400 V AC, 3-phase
480 V AC, 3-phase
Output Frequency f
2
Hz 0 - 50/60 (max. 500)
Switching frequency f
PWM
kHz 8
adjustable 4 - 32 (audible)
Operation Mode U/f control
Speed control with slip compensation
sensorless vector control (SLV)
PM motors
Synchronous reluctance motors
BLDC motors
Frequency resolution (setpoint value) Δf Hz 0.1
Rated operational current
At 150% overload I
e
A 9.5
Note Rated operational current at a switching frequency of 8 kHz and an ambient air
temperature of +50°C
Power loss
Heat dissipation at rated operational current I
e
=150 % P
V
W 136
Efficiency η % 96.6
Heat dissipation at current/speed [%]
Current = 100%
Speed = 0 % P
V
W 97
Speed = 50 % P
V
W 119
Speed = 90 % P
V
W 141
Current = 50 %
Speed = 0 % P
V
W 61
Speed = 50 % P
V
W 67
Speed = 90 % P
V
W 80
Current = 50 %
Speed = 0 % P
V
W 50
Speed = 50 % P
V
W 53
06/18/2021 Eaton 185755 ED2021 V80.0 EN 2 / 6