Data Sheet
Note Overload cycle for 60 s every 600 s
Note at 400 V, 50 Hz
150 % Overload P kW 0.75
Note at 440 - 480 V, 60 Hz
150 % Overload P HP 1
maximum permissible cable length I m screened: 50
screened, with motor choke: 100
unscreened: 75
unscreened, with motor choke: 150
Apparent power
Apparent power at rated operation 400 V S kVA 1.52
Apparent power at rated operation 480 V S kVA 1.83
Braking function
Standard braking torque max. 30 % MN
DC braking torque max. 100% of rated operational current I
e,
variable
Control section
Reference voltage U
s
V 10 V DC (max. 10 mA)
Analog inputs 2, parameterizable, 0 - 10 V DC, 0/4 - 20 mA
Analog outputs 1, parameterizable, 0 - 10 V
Digital inputs 4, parameterizable, max. 30 V DC
Digital outputs 1, parameterizable, 24 V DC
Relay outputs 1, parameterizable, N/O, 6 A (250 V, AC-1) / 5 A (30 V, DC-1)
Interface/field bus (built-in) OP-Bus (RS485)/Modbus RTU, CANopen®
Assigned switching and protective elements
Power Wiring
Safety device (fuse or miniature circuit-breaker)
IEC (Type B, gG), 150 % FAZ-B6/3
UL (Class CC or J) A 6
Mains contactor
150 % overload (CT/I
H
, at 50 °C) DILM7
DILEM-10
Main choke
150 % overload (CT/I
H
, at 50 °C) DX-LN3-004
Radio interference suppression filter (external, 150 %) DX-EMC34-008
Radio interference suppression filter, low leakage currents (external, 150 %) DX-EMC34-008-L
Note regarding radio interference suppression filter Optional external radio interference suppression filter for longer motor cable
lengths and for use in different EMC environments
Motor feeder
motor choke
150 % overload (CT/I
H
, at 50 °C) DX-LM3-008
Sine filter
150 % overload (CT/I
H
, at 50 °C) DX-SIN3-004
Design verification as per IEC/EN 61439
Technical data for design verification
Rated operational current for specified heat dissipation I
n
A 2.2
Heat dissipation per pole, current-dependent P
vid
W 0
Equipment heat dissipation, current-dependent P
vid
W 63.75
Static heat dissipation, non-current-dependent P
vs
W 0
Heat dissipation capacity P
diss
W 0
Operating ambient temperature min. °C -10
Operating ambient temperature max. °C 50
Operation (with 150 % overload)
IEC/EN 61439 design verification
10.2 Strength of materials and parts
10.2.2 Corrosion resistance Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures Meets the product standard's requirements.
06/16/2021 Eaton 185721 ED2021 V80.0 EN 3 / 6