Data Sheet

DATASHEET - DILDC600/22(RDS250)
DC contactor, 2 N/O, 2 NC, 1000 V: 600 A, RDS 250: 110 - 250 V 40 - 60
Hz/110 - 350 V DC, AC and DC operation
Part no. DILDC600/22(RDS250)
Catalog No. 183315
Alternate Catalog
No.
XTCE600DCM22A
Delivery program
Product range Contactors
Application DC contactor
Subrange Comfort devices greater than 170 A
Instructions DILDC contactors feature an electronic arc suppression system. Because of this,
it is important not to exceed any technical data limits in general – especially the
making and breaking capacity limits. Opening the device will immediately void the
warranty.
integrated suppressor circuit in actuating electronics
Connection technique Screw connection
Rated operational current, open
DC-1
Notes I
e
at 60 °C
1000 V I
e
A 600
Can be combined with auxiliary contact DILM820-XHI…
Actuating voltage RDS 250: 110 - 250 V 40 - 60 Hz/110 - 350 V DC
Voltage AC/DC AC and DC operation
Contacts
N/O = Normally open 2 N/O
N/C = Normally closed 2 NC
Auxiliary contacts
possible variants at auxiliary contact module fitting options on the side: 2 x DILM820-XHI11(V)-SI; 2 x DILM820-XHI11-SA
Side mounting auxiliary contacts
Technical data
General
Standards EN60947-4-1, EN60947-5-1
Lifespan, mechanical
AC operated Operations
x 10
6
1
DC operated Operations
x 10
6
1
Operating frequency, mechanical
AC operated Operations/h 1000
DC operated Operations/h 1000
Maximum operating frequency
electrical (Contactors without overload relay) Operations/h 100
Climatic proofing Damp heat, constant, to IEC 60068-2-78
Damp heat, cyclic, to IEC 60068-2-30
Ambient temperature
Open °C -40 - +70
Enclosed °C - 40 - + 40
Storage °C - 40 - + 80
06/16/2021 Eaton 183315 ED2021 V80.0 EN 1 / 5

Summary of content (5 pages)